10 Input Assemblies (Drive Produces)YASKAWA ELECTRIC SIEP C730600 28B V1000 Option SI-N3/V Technical Manual 51 Speed Status (Vendor Specific YE Assy) - 130 (0x82)InputInstance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 01300 FAULT ALARM READY SpeedAgree Fault Reset REVRunning ZSP Running1 – –Multi-FunctionPhoto Coupler2Multi-FunctionPhoto Coupler1Multi-FunctionDigital OutputLocal/Remote UV –2 Output Frequency (Low Byte)3 Output Frequency (High Byte)Parameter DataRunningRunning0: Stop1: Forward or Reverse RunningZSPZero Speed0: Running1: Stop or DC Injection BrakingREV RunningReverse Running0: Not Reverse Running1: Reverse RunningFault ResetFault Reset0: No Fault Reset1: Fault ResetSpeed AgreeSpeed Agree0: No Speed Agree1: Actual speed at speed referenceREADYDrive Ready0: Not Ready1: ReadyALARMDrive Alarm0: No Drive Alarm1: AlarmFAULTDrive Fault0: No Drive Fault1: FaultUVUnder Voltage0: No Under Voltage1: Under VoltageLocal/RemoteStatus of Run command from Network0: Run command is not from network1: Run command is from networkMulti-Function Digital OutputTerminal MA/MB0: Terminal MA/MB OFF1: Terminal MA/MB ONMulti-Function Photo Coupler 1Terminal P10: Terminal P1 OFF1: Terminal P1 ONMulti-Function Photo Coupler 2Terminal P20: Terminal P2 OFF1: Terminal P2 ONOutput FrequencyActual Drive SpeedMonitors drive output frequencyUnit depends on o1-03.Unit is not affected by Speed Scale SS.