Subject to change without notice. Printed in U.S.A. 350154-YTG-B-0408Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 350154-YTG-A-0108Johnson Controls Unitary Products5005 York DriveNorman, OK 73069Multipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above thelisted temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.HIGH CFMCOOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATIONOUTDOOR UNIT MODEL NO. CZH06011INDOOR COIL MODEL NO. FC62D + MV20DCONDENSERENTERING AIRTEMPERATUREID CFM 1750 1850 1950ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 7265T.C. 57.1 61.0 60.6 66.2 71.1 58.0 61.4 61.2 66.8 72.2 58.8 61.6 61.8 67.3 73.3S.C. 58.1 53.7 44.6 44.7 36.4 59.0 54.7 46.2 45.8 36.6 59.8 55.6 47.7 46.8 36.8K.W. 3.20 3.25 3.26 3.32 3.36 3.27 3.32 3.31 3.39 3.44 3.36 3.40 3.38 3.47 3.5375T.C. 55.3 58.5 58.0 63.4 68.2 56.0 58.8 58.4 63.9 68.9 56.7 59.1 58.7 64.3 69.5S.C. 56.3 52.5 43.9 43.6 34.8 57.0 53.5 44.9 44.6 34.9 57.7 54.5 45.8 45.6 34.9K.W. 3.69 3.74 3.74 3.80 3.86 3.77 3.80 3.79 3.87 3.93 3.85 3.88 3.86 3.95 4.0185T.C. 53.6 55.9 55.4 60.6 65.3 54.1 56.2 55.5 60.9 65.5 54.6 56.5 55.6 61.2 65.8S.C. 54.5 51.3 43.2 42.5 33.1 55.1 52.4 43.6 43.5 33.1 55.6 53.4 44.0 44.4 33.0K.W. 4.19 4.23 4.22 4.29 4.35 4.26 4.29 4.28 4.35 4.41 4.34 4.36 4.35 4.43 4.4995T.C. 51.8 53.3 52.8 57.8 62.4 52.2 53.6 52.7 58.0 62.2 52.6 53.9 52.5 58.2 62.0S.C. 52.7 50.1 42.5 41.5 31.5 53.1 51.3 42.4 42.3 31.4 53.5 52.4 42.1 43.2 31.2K.W. 4.69 4.71 4.70 4.77 4.84 4.76 4.77 4.76 4.83 4.90 4.83 4.85 4.83 4.91 4.97105T.C. 48.6 49.8 49.3 53.9 58.3 49.1 50.1 49.3 54.1 58.2 49.5 50.4 49.2 54.2 58.1S.C. 49.5 47.7 40.5 39.8 30.1 50.0 48.7 40.7 40.6 30.1 50.4 49.6 40.8 41.3 30.1K.W. 5.39 5.40 5.38 5.46 5.54 5.46 5.47 5.44 5.53 5.60 5.54 5.55 5.52 5.60 5.67115T.C. 45.6 46.3 46.0 50.2 54.3 46.1 46.7 46.0 50.3 54.3 46.5 47.1 46.0 50.4 54.2S.C. 46.4 45.4 38.6 38.2 28.7 46.9 46.2 39.0 38.9 29.0 47.4 46.9 39.4 39.6 29.1K.W. 6.06 6.07 6.04 6.13 6.22 6.14 6.14 6.11 6.20 6.28 6.23 6.22 6.19 6.28 6.36125T.C. 42.6 42.8 42.6 46.4 50.3 43.1 43.3 42.7 46.5 50.4 43.5 43.7 42.7 46.5 50.4S.C. 43.4 43.2 36.6 36.6 27.4 43.9 43.7 37.4 37.2 27.8 44.3 44.1 38.1 37.8 28.2K.W. 6.74 6.75 6.71 6.80 6.89 6.82 6.82 6.78 6.87 6.96 6.91 6.90 6.86 6.96 7.04NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.Air Handler Coil T.C. S.C. KWAV/SV60D – 0.96 0.96 0.99F4FV060 – 0.96 0.96 0.99MV20D FC/MC/PC60D 0.96 0.96 0.99MV20D UC60D 0.96 0.96 0.99MV20D FC/MC62D 1.00 1.00 1.00Variable SpeedFurnace Coil T.C. S.C. KWPV8*C20 FC/PC60C 0.95 0.95 1.00PV8*C20 FC/MC/PC60D 0.95 0.95 1.00PV8*C20 UC60D 0.95 0.95 1.00P(C,V)9*C20 FC/PC60C 0.93 0.93 0.99P(C,V)9*C20 FC/MC/PC60D 0.93 0.93 0.99P(C,V)9*C20 UC60D 0.93 0.93 0.99P(C,V)9*D20 FC/MC/PC60D 0.93 0.93 0.98P(C,V)9*D20 UC60D 0.93 0.93 0.98PV8*C20 FC/MC62D 0.98 0.98 1.01P(C,V)9*C20 FC/MC62D 0.97 0.97 1.00P(C,V)9*D20 FC/MC62D 0.97 0.97 0.99P(C,V)9*D20 HC60D 0.94 0.94 0.98