036-21318-002 Rev. A (0106)14 Unitary Products GroupMultipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above thelisted temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. EABA-F030SINDOOR COIL MODEL NO. F2RP/F2FP036CONDENSERENTERING AIRTEMPERATUREID CFM 850 1050 1250ID DB (°F) 85 80 70 85 80 70 85 80 70ID WB (°F) 72 67 57 72 67 57 72 67 5775T.C. 27.1 27.3 26.5 28.3 28.3 28.6 28.8 29.1 29.7S.C. 19.7 19.9 19.1 20.9 20.9 21.2 21.4 21.7 22.3KW 2.77 2.75 2.71 2.79 2.74 2.72 2.79 2.75 2.7285T.C. 27.3 26.9 26.9 29.1 28.4 27.9 30.0 29.8 29.3S.C. 19.9 19.5 19.5 21.7 21.0 20.5 22.6 22.4 21.9KW 2.95 2.90 2.86 2.98 2.91 2.87 2.99 2.93 2.8895T.C. 27.6 26.5 27.2 29.8 28.4 27.2 31.2 30.4 28.9S.C. 20.2 19.1 19.8 22.4 21.0 19.8 23.8 23.0 21.5KW 3.13 3.06 3.01 3.16 3.09 3.03 3.18 3.12 3.05105T.C. 26.6 25.6 25.4 29.0 27.7 26.5 30.6 29.6 28.2S.C. 19.2 18.2 18.0 21.6 20.3 19.1 23.2 22.2 20.8KW 3.29 3.22 3.15 3.32 3.25 3.18 3.34 3.28 3.20115T.C. 25.5 24.7 23.5 28.1 27.0 25.8 30.0 28.8 27.6S.C. 18.1 17.3 16.1 20.7 19.6 18.4 22.6 21.4 20.2KW 3.44 3.38 3.29 3.47 3.41 3.33 3.50 3.44 3.35125T.C. 24.5 23.9 21.7 27.3 26.4 25.0 29.4 28.0 26.9S.C. 17.1 16.5 14.3 19.9 19.0 17.6 22.0 20.6 19.5KW 3.60 3.53 3.43 3.63 3.56 3.48 3.66 3.59 3.50NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.Air Handler Coil T.C. S.C. KWN1AHB1206 G2FD030(S,H)17 0.97 0.94 1.00F2RP/F2FP030 0.98 1.00 1.00G1FA036S14 0.98 0.99 1.01G1FA036S17,21 0.97 0.97 1.00G1HD036 0.98 1.00 1.00G1NA030S17H 1.00 0.99 1.00G1NA030S21B 1.00 0.99 1.00G1UA036S14 0.98 0.99 1.01G1UA036S17,21 0.97 0.94 1.00G2FD030(S,H)17 0.97 0.94 1.00G2FD035(S,H)14 0.97 0.94 1.00G2FD036(S,H)17 0.98 0.95 1.00G2FD036(S,H)21 0.99 0.95 1.00