036-21323-002-C-0206Unitary Products Group 7TABLE 1: UNIT APPLICATION DATAApplication Limitations Minimum MaximumVoltage Variation (208/230-3-60) - Volts 187 253Voltage Variation (460-3-60) - Volts 414 506Voltage Variation (575-3-60) - Volts 540 630Ambient Air on Outdoor Coil (Cooling Cycle) - °F 45 115Ambient Air on Indoor Coil (Cooling Cycle) - °F 68 86TABLE 2: ARI RATINGS - COOLING AND SOUNDModel Cooling Capacity 1 Cond. UnitSound 2 Rated Airflow Rated ESPOutdoorUnit Indoor Unit MBH EER IPLV dB CFM IWGHB180 KB180 180 9.7 10.4 89.0 6000 0.35HB240 KB240 240 9.7 10.4 90.0 8000 0.401. Ratings are in accordance with ARI standard 340/360.2. Ratings are in accordance with ARI standard 370.TABLE 3: ELECTRICAL DATA COMPRESSORSModelNumberCompressorsPowerSupplySystem 1 System 2RLA LRA RLA LRAHB180 208/230-3-60 25.6 190.0 25.6 190.0HB180 460-3-60 12.8 95.0 12.8 95.0HB180 575-3-60 10.2 75 10.2 75HB240 208/230-3-60 42.0 239.0 42.0 239.0HB240 460-3-60 19.2 125.0 19.2 125.0HB240 575-3-60 13.8 80 13.8 80TABLE 4: ELECTRICAL DATA FAN MOTORSModelNumberCondenser FansPowerSupply Qty. FLAea.HB180 208/230-3-60 2 3.7HB180 460-3-60 2 1.85HB180 575-3-60 2 1.7HB240 208/230-3-60 2 5.8HB240 460-3-60 2 2.9HB240 575-3-60 2 2.2TABLE 5: ELECTRICAL DATA, OUTDOOR MCA & MAX. FUSE SIZEModelNumberPowerSupplyMin. CircuitAmpacityMax.FuseSize 1HB180 208/230-3-60 65.1 90HB180 460-3-60 32.5 45HB180 575-3-60 26.4 35HB240 208/230-3-60 106.1 125HB240 460-3-60 49.0 60HB240 575-3-60 35.5 451. Maximum fuse or maximum circuit breaker (HACR type per NEC).