036-21323-002-C-02068 Unitary Products GroupTABLE 6: OUTDOOR UNIT PHYSICAL DATADescriptionUnit ModelHB180 HB240Compressor 1 Rating - (Qty) Tons 2 X 7.5 = 15 Tons 2 X 10 = 20 TonsFansQuantity 2 2Diameter - inches 24 24Blades/Pitch (°) 3/34 3/32Nominal CFM 12,400 11,400Fan Motors 2 HP 1 1.5RPM 1140 1100CoilRows Deep X Rows High 2 X 30 2 X 30Finned Length - inches each slab 60 78Face Area - square feet (both slabs) 25 32.5Tube(Copper) OD - inches 3/8 3/8Fins(Aluminum) per inch 16 16Refrigerant - 22 (lbs -oz.)Holding Charge (sys1/sys2) 3 1 - 0 / 1 - 0 lbs. 1 - 0 / 1 - 0 lbs.Operating Charge (sys1/sys2) 4 14.0/14.0 lbs. 17.0/17.0 lbs.Unit Weight (lbs)Shipping 944 1380Operating 957 13961. These compressors are fully hermetic.2. The ball bearing, 56 frame, single phase condenser fan motors have internal protection and are directly connected to the condenser fans. Motorrotation is counterclockwise when viewing the lead end, which is opposite the shaft end.3. The amount of charge in the unit as shipped from the factory.4. Total operating charge for the condensing unit, matching indoor unit, and 25 feet of interconnecting pipe.TABLE 7: INDOOR UNIT PHYSICAL DATADescriptionUnit ModelLB180 LB240CoilRows Deep X Rows High 3 X 32 3 X 40Finned length- Inches 83 81Face Area - Square Feet 18.4 22.5Tube (Copper) OD - Inches 3/8 3/8Fins (Aluminum) per Inch 13 16Centrifugal Blower(Forward Curve - Qty) Diameter X Width - Inches 15 X 12 - 2 18 X 18 - 2Blower Motor1HP Field InstalledRPM -- --Filters(Throwaway)Quantity Per Unit 4/4 10Size - Inches 20 X 21 X 2 & 22 X 24 X 2 20 X 25 X2Total Face Area - Square Feet 25.8 34.7Unit Weight (lbs)Shipping 720 990Operating 830 1115Accessory OperatingWeight (lbs)Motor & Drive3HP 47 --5HP 120 120Supply Air Plenum 185 N/AReturn Air Grille 25 N/ABase 140 2101. Refer to Table 23 and 25 for more information.