5219967-UTG-A-0716Johnson Controls Unitary Products 13UNIT DIMENSIONSModel DimensionsA B C24 51-1/4 35-3/4 4730 51-1/4 35-3/4 4736 51-1/4 45-3/4 4942 51-1/4 45-3/4 4948 51-1/4 45-3/4 5360 51-1/4 45-3/4 55UNIT CLEARANCES 1 21. A 1" clearance must be provided between any combustible material and the supply air duct work.2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.Direction Distance (in.) Direction Distance (in.)Top33. Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.36 Power Entry (Right Side) 36Side Opposite Ducts 36 Left Side 24Duct Panel 0 Bottom 44. Units may be installed on combustible materials made from wood or class A, B or C roof covering materials only if factory base rails are left in place as shipped.1INDOOR BLOWER SPECIFICATIONSModel MotorHP RPM EFF. SF Frame24050, 30050 1/3 Variable 0.8 1.0 4824075, 30075, 36065 1/2 Variable 0.8 1.0 4836100, 42065. 42100,48065, 48100, 48125 3/4 Variable 0.8 1.0 4860065, 60100, 60125 1 Variable 0.8 1.0 48SOUND PERFORMANCEModel(Tons)Sound Rating 1dB (A)1. Rated in accordance with AHRI Standard 270.Octave Band Centerline Frequency (Hz)125 250 500 1000 2000 4000 800024 75 62.4 61.5 64.2 67 61 57.3 49.630 75 60.5 61.6 64.8 66.9 60.9 56.0 49.736 74 58.5 61.8 65.4 66.5 60.7 54.8 49.842 74 63.5 63.9 62.3 65 64 54.1 46.648 74 63.5 63.9 62.3 65 64 54.1 46.660 76 72.3 65.0 63.9 64 60 55.5 49.0HIGH VOLTAGECONNECTION 7/8”HIGH VOLTAGECONNECTION 1-3/32”COMPRESSORACCESS PANELCONDENSATEDRAIN BLOWERACCESSPANEL CONTROL ACCESSPANELLOW VOLTAGE CONNECTIONGAS SUPPLYEXHAUST HOODCOMBUSTION AIR INTAKEHEAT EXCHANGER ACCESS PANELBACA0296-001COIL GUARD