21APower supply V.ph.Hz. Consumption ACompressor FanModel Compressor FanPowersupply cablesection (2)Automaticswitch(K curve)(1)Start Nominal Start Nominal mm2400.3.50 400.3.50 94 14.6 17 2.8 4 20400.3.50 400.3.50 116 17.9 10 2.8 4 25400.3.50 400.3.50 127 18.1 31 4.9 6 32400.3.50 400.3.50 158 25.6 31 5.6 10 40400.3.50 400.3.50 2 x 94 2 x 14.6 2 x 17 2 x 3.9 10 50400.3.50 400.3.50 2 x 127 2 x 16.9 2 x 30 2 x 4.3 16 63400.3.50 400.3.50 2 x 158 2 x 18.8 2 x 38 2 x 7.4 25 80400.3.50 400.3.50 2 x 189 2 x 25.8 2 x 38 2 x 7.4 35 100SCOH090KSCOH076KSCOH070KSCOH180KSCOH240KSCOH300KSCOH120KSCOH150KFanFanModelPowersupply cablesectionStart NominalPower supply V.ph.Hz. Consumption Amm2400.3.50 8 2.2 4 x 1.5400.3.50 17 3.2 4 x 1.5400.3.50 17 3.4 4 x 1.5400.3.50 20 3.7 4 x 1.5400.3.50 34 6.1 4 x 1.5400.3.50 36 6.8 4 x 1.5400.3.50 68 9.8 4 X 2.5SICH070/076BSICH090BSICH150BSICH240BSICH300BSICH120BSICH180BElectrical characteristicsOutdoor unitsImportant: The dimensioning of the automatic switch and power supply line sections are orientative and should be corrected in accordance with jobsite conditions, length between units and legislation in force.Notes: 1.- K curve (DIN, VDE 0660-104). 2.- Based on copper conductors.Indoor unitsImportant: The dimensioning of the automatic switch and power supply line sections are orientative and should be corrected in accordance with jobsite conditions, length between units and legislation in force.