RATINGS®SUNLINE 2000MODEL DCG(Gas Heating)(OPTION / ACCESS.) DCE UNITSD*CG UNITS(OPTION / ACCESSORY)THROWAWAYALUMINIZED STEELFEMALEModel Rating1PointTotal Output,Mbh / kWTotal Input,kW COP2 EER3 Sensible Output,Mbh / kWLatent Output,Mbh / kWElectric Heat4Nominal Capacity,kWD3CE180T1 159 / 46.6 18.2 2.60 8.80 132 / 38.7 26.9 / 7.9T2 142 / 41.7 20.0 2.10 7.15 141 / 41.2 1.6 / 0.5 18, 36, 54, 72T3 152 / 44.6 16.4 2.75 9.40 119 / 34.9 33.2 / 9.7D3CE240T1 210 / 61.5 24.8 2.50 8.50 176 / 51.5 34.0 / 10.0T2 182 / 53.3 27.1 2.00 6.75 182 / 53.3 0.0 / 0.0 18, 36, 54, 72T3 196 / 57.5 22.2 2.60 8.80 152 / 44.6 42.6 / 12.51T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.2COP = Coefficient of Performance - total output kW divided by the total input kW.3EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.4Heaters available as factory-installed options or field-installed accessories - all with single point power supply.CAPACITY RATINGS - Cooling / Electric HeatingModel Cooling Capacity,Mbh / kWGas Heat CapacityInput (Net)Mbh / kWOutputMbh / kWGas Rate*cfh / m3/hTemp. Rise (°F / °C)At Full InputMin. Max.D3CG180N320 180 / 52.7 291 / 85.2 258 / 75.6 302 / 8.5 30 / 17 60 / 33D3CG240N320 240 / 70.3NOTE: Gas Heaters are shipped available for natural gas, but can be converted to L.P. / propane gas with a field-installed conversion accessory. All gas units are two-stage heating.First stage is 50% of total.*Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m3).CAPACITY RATINGS - Gas Heating530.26-TG3YIUnitary Products Group 3