COOLING CAPACITIES (CFM Air Flow) - 180 UNITSAir OnEvaporator Coil TotalCap.1MBHPowerInput2kWSensible Capacity1, MBHEntering Dry Bulb Temp., °FCFM WB °F 90 86 82 79 75 72@80°F Air Temperature on Condenser Coil1720073 227 14.7 175 151 126 102 78 -70 213 14.4 200 176 152 127 103 7966 199 14.0 199 199 177 153 128 10463 193 14.0 193 193 190 166 142 11759 188 13.9 188 188 188 176 152 128593073 210 14.5 157 136 115 93 72 -70 197 14.2 180 159 138 116 95 7466 184 13.9 184 182 160 139 118 9763 179 13.8 179 179 172 151 130 10959 174 13.7 174 174 174 163 142 121445073 195 14.3 127 111 95 79 63 -70 183 14.0 146 130 114 98 82 6666 171 13.6 165 149 133 117 101 8663 166 13.6 166 159 143 127 111 9659 162 13.5 162 162 153 137 121 105@95°F Air Temperature on Condenser Coil720073 207 15.9 170 146 122 98 74 -70 195 15.5 195 171 147 123 99 7566 183 15.2 183 183 172 148 124 10063 179 15.1 179 179 179 159 135 11159 174 15.0 174 174 174 162 138 113593073 192 15.9 150 129 108 87 66 -70 181 15.6 172 151 130 109 88 6766 170 15.2 170 170 153 132 110 8963 166 15.1 166 166 162 141 120 9959 161 15.0 161 161 161 151 130 109445073 177 15.6 123 107 91 75 59 -70 167 15.3 142 126 110 94 78 6266 157 14.9 157 145 129 113 97 8163 153 14.8 153 153 137 121 105 8959 149 14.7 149 149 145 129 113 97@115°F Air Temperature on Condenser Coil720073 169 18.2 157 133 109 85 61 -70 161 17.6 161 158 134 110 85 6166 154 17.1 154 154 154 135 110 8663 149 17.1 149 149 149 137 112 8859 144 17.1 144 144 144 132 107 83593073 169 17.8 141 120 99 78 57 -70 161 17.2 161 142 121 100 79 5866 153 16.6 153 153 144 123 102 8163 148 16.6 148 148 148 128 107 8659 143 16.6 143 143 143 133 112 90445073 159 17.5 114 98 82 66 50 -70 151 17.0 133 117 101 85 69 5366 144 16.4 144 136 120 104 88 7263 139 16.4 139 139 124 108 92 7659 135 16.4 135 135 128 112 96 801These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of thesupply air blower motor.2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.530.26-TG3YIUnitary Products Group 5