127915-YIM-A-040534 Unitary Products GroupNOTE 1: HACR Type per NEC.TABLE 12: DR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR WITH POWERED CONVENIENCE OUTLETMODELTONNAGE VOLTAGECOMPRESSORS OD FANMOTORSFLA EACHIDBLOWERMOTORFLACONVOUTLETAMPSHEATER OPTION MIN.CIRCUITAMPACITY(AMPS)MAX. FUSE/BRKR1SIZE(AMPS)RLAEACHLRAEACH MODEL KW STAGES AMPS15208 22.4 164 2.1 20 10.0None 0.0 - - 88.8 110E18 13.5 1 37.5 88.8 110E36 27.0 2 75.1 131.2 150E54 40.6 2 112.6 178.4 200E72 54.1 2 150.1 187.7 200230 22.4 164 2.1 20 10.0None 0.0 - - 88.8 110E18 18.0 1 43.3 91.6 110E36 36.0 2 86.6 145.8 150E54 54.0 2 129.9 167.4 175E72 72.0 2 173.2 210.7 225460 10.9 100 1.1 10 5.0None 0.0 - - 43.9 50E18 18.0 1 21.7 45.8 50E36 36.0 2 43.3 72.9 80E54 54.0 2 65.0 83.7 90E72 72.0 2 86.6 105.4 110575 8.3 78 0.9 8.2 4.0None 0.0 - - 34.5 40E18 18.0 1 17.3 36.9 40E36 36.0 2 34.6 58.6 60E54 54.0 2 52.0 67.2 70E72 72.0 2 69.3 84.5 9020208 33.6 225 3.7 28 10.0None 0.0 - - 127.0 150E18 13.5 1 37.5 127.0 150E36 27.0 2 75.1 139.4 150E54 40.6 2 112.6 186.6 200E72 54.1 2 150.1 195.9 200230 33.6 225 3.7 26.6 10.0None 0.0 - - 127.0 150E18 18.0 1 43.3 127.0 150E36 36.0 2 86.6 154.0 175E54 54.0 2 129.9 175.7 200E72 72.0 2 173.2 219.0 225460 17.3 114 1.9 13.3 5.0None 0.0 - - 64.8 80E18 18.0 1 21.7 64.8 80E36 36.0 2 43.3 77.0 80E54 54.0 2 65.0 87.8 90E72 72.0 2 86.6 109.5 110575 13.5 80 1.5 10.3 4.0None 0.0 - - 50.7 60E18 18.0 1 17.3 50.7 60E36 36.0 2 34.6 61.2 70E54 54.0 2 52.0 69.8 70E72 72.0 2 69.3 87.2 9025208 47.1 245 3.7 38.6 10.0None 0.0 - - 169.4 200E18 13.5 1 37.5 169.4 200E36 27.0 2 75.1 169.4 200E54 40.6 2 112.6 201.6 225E72 54.1 2 150.1 210.9 225230 47.1 245 3.7 38.6 10.0None 0.0 - - 169.4 200E18 18.0 1 43.3 169.4 200E36 36.0 2 86.6 169.4 200E54 54.0 2 129.9 190.7 225E72 72.0 2 173.2 234.0 250460 19.6 125 1.9 19.3 5.0None 0.0 - - 76.0 90E18 18.0 1 21.7 76.0 90E36 36.0 2 43.3 84.5 90E54 54.0 2 65.0 95.3 110E72 72.0 2 86.6 117.0 125575 15.8 100 1.5 15.4 4.0None 0.0 - - 61.0 70E18 18.0 1 17.3 61.0 70E36 36.0 2 34.6 67.6 70E54 54.0 2 52.0 76.2 90E72 72.0 2 69.3 93.5 100VOLTAGE LIMITATIONS ELECTRIC HEAT CORRECTION FACTORSPOWER SUPPLY VOLTAGE NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIERMIN. MAX. 208 208 1.00VOLTAGELIMITATIONS1208/230-3-60 187 253 240 230 0.92460-3-60 414 506 480 460 0.92565-3-60 518 630 600 575 0.921. Utilization Range “A” in accordance with ARI Standard 110.