127915-YIM-A-040542 Unitary Products GroupTABLE 17: DR180 BLOWER PERFORMANCE - HIGH STATIC DRIVE (COOLING ONLY)ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP0.2 8032 1168 6.346 7.80 7765 1129 5.808 7.14 7396 1092 5.143 6.32 7225 1053 4.552 5.60 6936 1013 4.209 5.18 6573 972 3.730 4.48 6271 933 3.307 3.970.4 7747 1166 6.122 7.53 7479 1125 5.525 6.79 7095 1091 4.860 5.98 6907 1054 4.347 5.35 6610 1013 3.936 4.72 6270 973 3.438 4.13 5923 934 3.046 3.660.6 7490 1170 5.841 7.18 7161 1131 5.268 6.48 6792 1093 4.602 5.66 6578 1054 4.074 5.01 6243 1013 3.657 4.39 5955 974 3.197 3.84 5512 933 2.869 3.440.8 7209 1170 5.551 6.83 6841 1132 4.967 6.11 6508 1094 4.347 5.35 6292 1055 3.969 4.76 5875 1014 3.418 4.10 5575 974 3.005 3.61 5153 935 2.550 3.061.0 6905 1171 5.247 6.45 6531 1133 4.642 5.71 6223 1095 4.118 5.06 5952 1055 3.658 4.39 5535 1015 3.102 3.72 5144 975 2.686 3.22 4689 936 2.392 2.871.2 6583 1172 4.948 6.08 6203 1134 4.397 5.41 5866 1097 3.803 4.56 5585 1057 3.388 4.07 5091 1017 2.899 3.48 4686 976 2.471 2.971.4 6252 1175 4.658 5.73 5836 1136 4.057 4.87 5502 1098 3.596 4.32 5166 1058 3.095 3.71 4617 1017 2.598 3.121.6 5823 1177 4.324 5.32 5457 1138 3.790 4.55 5075 1099 3.285 3.94 4670 1059 2.801 3.361.8 5427 1179 4.066 4.88 5032 1139 3.483 4.18 4585 1100 2.891 3.472.0 4986 1180 3.632 4.36 4520 1141 3.241 3.897.5 HP motor 5 HP motorChart shading corresponds to minimum motor horsepower requirements as defined below.15 Ton High Static Drive Blower Performance (Horizontal Discharge)0 turns 1 turn 2 turns 3 turns 4 turns 5 turns 6 turns15-ton High Static DriveVP60 & BK904500500055006000650070007500800085000.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0External Static ("WC)SCFM1 Turn0 Turns3 Turns5 Turns6 Turns2 Turns4 Turns