Johnson Controls Unitary Products 27Multipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listedtemperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.COOLING PERFORMANCE DATACONDENSING UNIT MODEL NO. YHJD60S41S1INDOOR COIL MODEL NO. FC/MC62CONDENSINGENTERING AIRTEMPERATUREIDCFM 1600 1800 2000ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 7265T.C. 54.0 57.1 56.9 62.3 67.6 56.0 57.9 57.8 63.4 69.1 58.0 58.7 58.7 64.4 70.5S.C. 54.0 51.0 43.4 42.9 34.8 56.0 54.4 45.4 45.0 36.2 58.0 57.7 47.4 47.1 37.6KW 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.975T.C. 51.9 54.1 53.9 59.2 64.5 53.7 54.9 54.8 60.2 65.7 55.5 55.7 55.6 61.2 66.9S.C. 51.9 49.8 42.0 41.7 33.5 53.7 52.7 44.1 43.8 34.8 55.5 55.6 46.1 45.8 36.2KW 3.2 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.385T.C. 49.7 51.1 51.0 56.2 61.4 51.3 51.9 51.8 57.1 62.4 53.0 52.7 52.6 58.0 63.4S.C. 49.7 48.6 40.7 40.5 32.2 51.3 51.1 42.8 42.5 33.4 53.0 52.7 44.9 44.6 34.7KW 3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.7 3.7 3.6 3.6 3.6 3.7 3.795T.C. 47.6 48.1 48.1 53.1 58.3 49.0 48.9 48.8 54.0 59.0 50.4 49.7 49.5 54.8 59.8S.C. 47.6 47.4 39.3 39.2 30.9 49.0 48.9 41.5 41.3 32.0 50.4 49.7 43.6 43.3 33.2KW 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.1 4.1 4.0 4.0 4.0 4.1 4.1105T.C. 44.3 44.6 44.1 48.7 53.5 45.6 45.5 44.6 49.3 54.1 46.8 46.3 45.2 50.0 54.7S.C. 44.3 44.6 37.6 37.4 29.0 45.6 45.5 39.7 39.4 30.2 46.8 46.3 41.8 41.5 31.3KW 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.5 4.6115T.C. 41.1 41.3 40.2 44.4 48.9 42.2 42.2 40.6 44.9 49.4 43.3 43.1 41.0 45.3 49.9S.C. 41.1 41.3 35.9 35.7 27.3 42.2 42.2 37.9 37.7 28.4 43.3 43.1 40.0 39.7 29.5KW 4.9 5.0 4.9 5.0 5.0 5.0 5.0 4.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0125T.C. 37.9 37.9 36.2 40.1 44.3 38.8 38.8 36.5 40.4 44.6 39.8 39.8 36.8 40.7 45.0S.C. 37.9 37.9 34.2 33.9 25.5 38.8 38.8 36.2 35.9 26.6 39.8 39.8 36.8 37.9 27.7KW 5.4 5.4 5.4 5.4 5.5 5.4 5.4 5.4 5.4 5.5 5.4 5.4 5.4 5.4 5.5NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.Air Handlers Coils T.C. S.C. KWAHX60 – 1.06 1.13 1.05F6FP060 – 1.06 1.09 1.01MA20D MC62D 1.00 1.00 1.00MV20D MC62D 1.01 1.01 1.00Furnaces Coils T.C. S.C. KWT*(8,L)X*C20 FC/MC62D 1.05 1.08 0.99T*9X*D20 FC/MC62D 1.02 1.02 1.02Y*9C*D20 FC/MC/PC60D 0.99 0.96 0.97Y*(8,L)C*C20 FC/MC62D 1.00 0.97 0.96Y*9C*C20 FC/MC62D 0.99 0.96 0.98