5808009-YIM-A-0320Johnson Controls Ducted Systems 53ZB150 (12.5 Ton) Side DuctAir Flow(CFM)Available External Static Pressure - IWG 11. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied Drive Standard 3 HP & Drive3200 713 0.88 764 1.09 814 1.28 861 1.47 907 1.65 952 1.83 995 2.00 1037 2.17 1079 2.34 1119 2.523400 728 1.02 779 1.23 829 1.43 877 1.61 923 1.79 967 1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.663600 745 1.18 796 1.39 846 1.59 893 1.77 939 1.95 984 2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.823800 763 1.36 815 1.57 864 1.76 912 1.95 958 2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.004000 783 1.55 835 1.76 884 1.96 932 2.15 978 2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.194200 805 1.77 856 1.98 906 2.17 953 2.36 999 2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.414400 828 2.00 879 2.21 929 2.41 976 2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29 1194 3.46 1235 3.644600 852 2.25 904 2.46 953 2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37 1177 3.54 1219 3.72 1259 3.894800 879 2.52 930 2.73 980 2.93 1027 3.12 1073 3.30 1118 3.47 1161 3.65 1203 3.82 1245 3.99 1285 4.165000 906 2.81 958 3.02 1007 3.22 1055 3.41 1101 3.59 1146 3.76 1189 3.94 1231 4.11 1273 4.28 1313 4.455200 936 3.12 987 3.33 1037 3.53 1084 3.72 1130 3.90 1175 4.07 1218 4.24 1260 4.42 1302 4.59 1343 4.765400 966 3.45 1018 3.66 1067 3.86 1115 4.05 1161 4.23 1206 4.40 1249 4.57 1291 4.74 1333 4.91 1373 5.095600 999 3.80 1050 4.01 1100 4.20 1147 4.39 1193 4.57 1238 4.75 1281 4.92 1323 5.09 1365 5.26 1405 5.445800 1032 4.16 1084 4.37 1133 4.57 1181 4.75 1227 4.93 1271 5.11 1315 5.28 1357 5.45 1398 5.62 - -6000 1067 4.54 1119 4.75 1168 4.95 1216 5.13 1262 5.31 1306 5.49 1350 5.66 - - - - - -6200 1103 4.94 1155 5.15 1204 5.34 1252 5.53 1298 5.71 - - - - - - - - - -Hi Static 5 HP & Drive 5 HP & Field Supplied Drive