6021980-UIM-A-1120Johnson Controls Ducted Systems 59Additional static resistance - ZT078 through 150Size (tons) Model CFM Cooling only11. Add these values to the available static resistance in the respective blower performance tables.Reheat coil 2 3 Economizer2 32. Deduct these values from the available external static pressure shown in the respective blower performance tables.3. The pressure drop through the economizer is greater for 100% outdoor air than it is for 100% return air. If the resistance of the return airduct is less than 0.25 IWG, the unit delivers less CFM during full economizer operation.4 in. Filter2 Electric heat kW 209 18 24 36 54078 (6.5)090 (7.5)102 (8.5)120 (10)150 (12.5)ZT1900 0.03 0.07 0.04 0.12 0.05 0.06 0.07 0.08 0.102100 0.04 0.08 0.10 0.13 0.06 0.07 0.08 0.09 0.112300 0.06 0.09 0.17 0.14 0.07 0.08 0.09 0.10 0.132500 0.08 0.10 0.23 0.16 0.08 0.09 0.10 0.11 0.142700 0.10 0.11 0.29 0.17 0.09 0.10 0.12 0.13 0.162900 0.12 0.12 0.34 0.19 0.10 0.11 0.13 0.14 0.183100 0.15 0.13 0.40 0.20 0.12 0.13 0.15 0.16 0.203300 0.17 0.14 0.45 0.22 0.13 0.14 0.17 0.18 0.223500 0.20 0.15 0.51 0.26 0.15 0.16 0.19 0.20 0.243700 0.22 0.17 0.56 0.27 0.17 0.18 0.21 0.22 0.263900 0.25 0.18 0.61 0.29 0.19 0.20 0.23 0.24 0.284100 0.28 0.19 0.66 0.32 0.21 0.22 0.25 0.26 0.314300 0.31 0.20 0.70 0.35 0.23 0.24 0.28 0.29 0.344500 0.34 0.21 0.75 0.38 0.25 0.26 0.30 0.31 0.374700 0.38 0.22 0.79 0.41 0.28 0.29 0.33 0.34 0.404900 0.41 0.24 0.83 0.44 0.30 0.31 0.35 0.37 0.435100 0.45 0.25 0.87 0.47 0.33 0.34 0.38 0.40 0.465300 0.48 0.26 0.91 0.51 0.35 0.37 0.41 0.43 0.495500 0.52 0.27 0.95 0.55 0.38 0.40 0.44 0.46 0.535700 0.56 0.28 0.98 0.58 0.41 0.43 0.47 0.49 0.565900 0.60 0.30 1.02 0.62 0.44 0.46 0.50 0.53 0.596100 0.64 0.31 1.05 0.67 0.47 0.49 0.53 0.56 0.626300 0.69 0.32 1.08 0.71 0.50 0.53 0.56 0.59 0.65