May be subject to change Page 24 of 33HumidityIn the “Humidity” menu it is possible to regulate the ventilation step in accordance with the humiditylevel.Low ventilation step is only active in wintertime and at humidity levels below 30%.High ventilation step is activated when the humidity rises 10% or more compared to the averagehumidity level the last 24 hours. High ventilation step is deactivated when humidity drops 3% ormore compared to the average humidity level the last 24 hours.It can last up to 3 minutes before high/low ventilation step i stabilized.” ” indicates that the menu point flashes and can be set to another value.Use of the CTS602 panel:- press ESC to go one step back in the menu- press qpto move up or down in a menu or to adjust anactivated menu- press ENTER to activate a menu- press ENTER to confirm a menu- press OFF to turn off the unit- press ON to turn the unit onHUMIDITY FLOWLOW 1ENTER ENTEROption of choosing lowventilation step at lowhumidity.The value can be set to: OFFand 1, 2, 3, .FLOWHIGH 4ENTER ENTERFLOWHIGH ”4”TIME0 MINENTER ENTERTIME0 MINHUMIDITYLOW ”1"ENTEROption of choosinghigh ventilationstep at highhumidity.The value can beset to: OFF and 2,3, 4.Adjustable rangebetween 15...45%Standard is 30 %LOW30%ENTER”30"%ENTERMaximal duration for highventilation step caused byhigh humidity."LOWFigure 18: The ”Humidity" menu