May be subject to change page 24 of 27Temp. controlIn the ”Temp. control” menu it is possible to set the highest and lowest inlet temperature.” ” indicates that the menu point flashes and can be set to another value.Use of t he CTS 600 panel :- pr ess ESC t o go one st ep back i n t he menu- pr ess qpt o move up or down i n a menu or t oadj ust an act i vat ed menu- pr ess ENTER t o act i vat e a menu- pr ess ENTER t o conf i r m a menu- pr ess OFF t o t ur n of f t he uni t- pr ess ON t o t ur n t he uni t onCooling via compressor isallowed at outdoortemperatures higher thanthe preset value.Can be set from 14-22°CWINTER”MIN 16°C”ENTERSUMMER”MIN 14°C”Cooling via compressor isallowed at outdoortemperatures higher thanthe preset value.Can be set from 10-16°CTEMP.CONTROLENTER ENTERENTERSUMMERMAX ”22°C”Lowest out-door temperature inorder for the unit to operateaccording to summer temperatures.WINTERMAX ”24°C”ENTERENTERSUMMER”12°C”Highest possible inlet temperature inwinter.Can be set from 22-50 °C.Highest possible inlet temperature insummer.Can be set from 16-25 °C.These are onlyshown in the panelif the unit has aheating surface.Figure 18: The ”Temp. control” menu