Communication with M-Bus2CMC48001M0201 279 A43/A44Revision: C User Manual10.5.10 Reset of stored state for input 1Reset of stored state for input 1 is performed by sending the following command(all values are hexadecimal). The command is not affected by the write protectionlevel set.Byte No. Size Value Description1 1 68 Start character2 1 08 L-field, calculated from C field to last user data3 1 08 L-field, repeated4 1 68 Start character5 1 53/73 C-field, SND_UD6 1 xx A-field, address7 1 51 CI-field, data send, LSB first8 1 C0 DIF size, no data, storage number 19 1 40 DIFE unit=110 1 FD VIF extension of VIF codes11 1 9B VIFE digital input12 1 07 VIFE clear13 1 xx CS checksum, calculated from C field to last data14 1 16 Stop character10.5.11 Reset of stored state for input 2Reset of stored state for input 2 is performed by sending the following command(all values are hexadecimal). The command is not affected by the write protectionlevel set.Byte No. Size Value Description1 1 68 Start character2 1 09 L-field, calculated from C field to last user data3 1 09 L-field, repeated4 1 68 Start character5 1 53/73 C-field, SND_UD6 1 xx A-field, address7 1 51 CI-field, data send, LSB first8 1 C0 DIF size, no data, storage number 19 1 80 DIFE unit=010 1 40 DIFE unit=211 1 FD VIF extension of VIF codes12 1 9B VIFE digital input13 1 07 VIFE clear14 1 xx CS checksum, calculated from C field to last data15 1 16 Stop character