Meter SettingsA43/A44 34 2CMC48001M0201User Manual Revision: C4.1.2 Setting TimeTo set the time, perform the following steps:1. Choose the Settings icon in the main menu, press .2. Choose “Clock”, press .3. The display will now show the date. Press to get to the time-menu.4. Set the time.4.1.3 Setting RatiosTo set the ratios, perform the following steps:1. Choose the Settings icon in the main menu, press .2. Choose “Ratios”, press .3. The display will show the quantity Current (CT on the display) and theratio. To change the ratio, press . See table 4:1 for interval.4. Press . The display will show the quantity Voltage (VT on the display)and the ratio. To change the ratio, press . See table 4:1 for interval.Table: 4:1Option IntervalTransformer Current (CT on the dis- 1-9999/1-9play)Transformer Voltage (VT on the dis- 1-999999/1-999play)4.1.4 Setting WiresThe meter can either use three wires TPE or four wires TPE+N. To set thenumber of wires, perform the following steps:1. Choose the Settings icon in the main menu, press .2. Choose “Wires”, press .3. The display will now show the wire configuration used by the meter.4. Set the number of wires.4.1.5 Setting Pulse OutputTo set the pulse output, perform the following steps:1. Choose the Settings icon in the main menu, press .2. Choose “Pulse out” (Pul.out on the display), press .The display will show what type of energy is measured on pulse output 1.Depending on meter type, the available choices are:Act.Nrg.Imp on the display Active energy importedAct.Nrg.Exp on the display Active energy exportedReact.Nrg.Imp on the display Reactive energy importedReact.Nrg.Exp on the display Reactive energy exportedInactive on the display Inactive3. Set the energy type.