Meter Settings2CMC48001M0201 35 A43/A44Revision: C User Manual4. Press once to get to the next menu. The display will show the frequency.The interval that can be set is 0-999999 imp/kWh or 0-999999 imp/MWh.Set the frequency and quantity.5. Press once to get to the next menu. The display will show thepulse length in milliseconds. The interval for the pulse length is from10 to 990ms. Set the pulse length.6. Press once to get to the next menu. The display will show the setting forpulse output 1. Depending on the meter type, the available choices are:4 configurable I/Os 4 static I/Os 1 static I/ONo output No output No outputOut 1 Out 1 Out 1Out 2 Out 2 -Out 3 - -Out 4 - -Note – If choosing an I/O that is not pulse output configured, the option is set to “nooutput” when pressing the button.7. The first pulse output is now fully configured. Depending on the metertype, up to four pulse outputs can be set. If your meter supports multiplepulse outputs, use to toggle down to the remaining pulse outputs andset them the same way as pulse output 1.4.1.6 Setting I/OTo set the I/O, perform the following steps:1. Choose the Settings icon in the main menu, press .2. Choose “I/O”, press .3. The display will now show I/O 1. To change I/O, use or . To set anI/ O, press the button. Depending on the meter type, different choicescan be made for the I/O, see table 4:2.Table: 4:2I/O Available choices4 configurable I/Os • Input• Alarm out• Communication out (Comm.out on display)• Pulse out (Pul.out on display)• Tariff out1• Always on• Always off4 static I/Os2 • Alarm out• Communication out (Comm.out on display)• Pulse out (Pul.out on display)• Tariff out3• Always on• Always off