314 Technical dataElectric power network specificationVoltage (U1 ) 200/208/220/230/240 V AC 3-phase for 200 V AC drives380/400/415/440/460/480 V AC 3-phase for 400 V AC drives±10% variation from converter nominal voltage is allowed as default.Short-circuit capacity Maximum allowed prospective short-ci rcuit current at the input powerconnection as defined in IEC 60439-1 is 100 kA. The drive is suitablefor use in a circuit capable of delivering not more than 100 kA rmssymmetrical amperes at the drive maximum rated voltage.Frequency 50/60 Hz ± 5%, maximum rate of change 17%/sImbalance Max. ±3% of nominal phase to phase input voltageMotor connection dataVoltage (U2 ) 0 to U1 , 3-phase symmetrical, Umax at the field weakening pointShort-circuit protection(IEC 61800-5-1,UL 508C)The motor output is short-circuit proof by IEC 61800-5-1 andUL 508C.Frequency 0…500 HzFrequency resolution 0.01 HzCurrent See section Ratings on page 308.Power limit 1.5 · PNField weakening point 10…500 HzSwitching frequency 4, 8, 12 or 16 kHzMaximumrecommendedmotor cable lengthR0: 30 m (100 ft), R1…R4: 50 m (165 ft)With output chokes the motor cable length may be extended to 60 m(195 ft) for R0 and 100 m (330 ft) for R1…R4.To comply with the European EMC Directive, use the cable lengthsspecified in the table below for 4 kHz switching frequency. Thelengths are given for using the drive with the internal EMC filter or anoptional external EMC filter.4 kHz switchingfrequencyInternal EMC filter Optional externalEMC filterSecond environment(category C3 1))30 m (100 ft) 30 m (100 ft)minimumFirst environment(category C2 1))- 30 m (100 ft)1) See the new terms in section Definitions on page 318.Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com