316 Technical dataAmbient conditionsEnvironmental limits for the drive are given below. The drive is to beused in a heated indoor controlled environment.Operationinstalled forstationary useStoragein the protectivepackageTransportationin the protectivepackageInstallation site altitude 0 to 2000 m (6600 ft)above sea level(above 1000 m[3300 ft], see sectionDerating on page309)- -Air temperature -10 to +50 °C (14 to122 °F). No frostallowed. See sectionDerating on page309.-40 to +70 °C (-40 to+158 °F)-40 to +70 °C (-40 to+158 °F)Relative humidity 0 to 95% Max. 95% Max. 95%No condensation allowed. Maximum allowed relative humidity is60% in the presence of corrosive gases.Contamination levels(IEC 60721-3-3,IEC 60721-3-2,IEC 60721-3-1)No conductive dust allowed.According toIEC 60721-3-3,chemical gases:Class 3C2solid particles: Class3S2.The drive must beinstalled in clean airaccording toenclosureclassification. Coolingair must be clean,free from corrosivematerials andelectricallyconductivedust.According toIEC 60721-3-1,chemical gases:Class 1C2solid particles: Class1S2According toIEC 60721-3-2,chemical gases:Class 2C2solid particles: Class2S2Sinusoidal vibration(IEC 60721-3-3)Tested according toIEC 60721-3-3,mechanicalconditions: Class 3M42…9 Hz, 3.0 mm(0.12 in)9…200 Hz, 10 m/s 2(33 ft/s 2 )- -Shock(IEC 60068-2-27,ISTA 1A)- According to ISTA 1A.Max. 100 m/s2(330 ft/s2 ), 11 ms.According to ISTA 1A.Max. 100 m/s 2(330 ft/s2 ), 11 ms.Free fall Not allowed 76 cm (30 in) 76 cm (30 in)Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com