176 Actual signals and parametersFieldbus equivalentExample: If 2017 MAX TORQUE 1 (see page 217) is set from an external controlsystem, an integer value of 1000 corresponds to 100.0%. All the read and sent valuesare limited to 16 bits (-32768…32767).Default values with different macrosWhen application macro is changed (parameter 9902 APPLIC MACRO), the softwareupdates the parameter values to their default values. The table below shows theparameter default values for different macros. For other parameters, the defaultvalues are the same for all macros (shown in the parameter list starting on page 185).Note: It is possible to control several functions with one input (DI or AI), and there is achance of mismatch between these functions. In some cases it is desired to controlseveral functions with one input.For example in the ABB standard macro, DI3 and DI4 are set to control constantspeeds. On the other hand, it is possible to select value 6 (DI3U,4D) for parameterIndex Name/SelectionABBSTANDARD3-WIRE ALTERNATEMOTORPOTHAND/AUTOPIDCONTROLTORQUECONTROL9902 APPLICMACRO1 =ABBSTANDARD2 =3-WIRE3 =ALTERNATE4 =MOTORPOT5 =HAND/AUTO6 =PIDCONTROL7 =TORQUECTRL1001 EXT1COMMANDS2 = DI1,2 4 =DI1P,2P,39 = DI1F,2R 2 = DI1,2 2 = DI1,2 1 = DI1 2 = DI1,21002 EXT2COMMANDS0 = NOTSEL0 = NOTSEL0 = NOTSEL0 = NOTSEL21 = DI5,4 20 = DI5 2 = DI1,21003 DIRECTION 3 =REQUEST3 =REQUEST3 =REQUEST3 =REQUEST3 =REQUEST1 =FORWARD3 =REQUEST1102 EXT1/EXT2SEL0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 3 = DI3 2 = DI2 3 = DI31103 REF1 SELECT 1 = AI1 1 = AI1 1 = AI1 12 =DI3U,4D(NC)1 = AI1 1 = AI1 1 = AI11106 REF2 SELECT 2 = AI2 2 = AI2 2 = AI2 2 = AI2 2 = AI2 19 =PID1OUT2 = AI21201 CONSTSPEED SEL9 = DI3,4 10 = DI4,5 9 = DI3,4 5 = DI5 0 = NOTSEL3 = DI3 4 = DI41304 MINIMUM AI2 1.0% 1.0% 1.0% 1.0% 20.0% 20.0% 20.0%1501 AO1CONTENT SEL103 102 102 102 102 102 1021601 RUN ENABLE 0 = NOTSEL0 = NOTSEL0 = NOTSEL0 = NOTSEL0 = NOTSEL4 = DI4 0 = NOTSEL2201 ACC/DEC 1/2SEL5 = DI5 0 = NOTSEL5 = DI5 0 = NOTSEL0 = NOTSEL0 = NOTSEL5 = DI53201 SUPERV 1PARAM103 102 102 102 102 102 1023401 SIGNAL1PARAM103 102 102 102 102 102 1029904 MOTOR CTRLMODE3 =SCALAR:FREQ1 =VECTOR:SPEED1 =VECTOR:SPEED1 =VECTOR:SPEED1 =VECTOR:SPEED1 =VECTOR:SPEED2 =VECTOR:TORQ