98 ACS550 Userís ManualParametersComplete parameter descriptionsThis section describes the actual signals and parameters for ACS550.Group 99: START-UP DATAThis group defines special start-up data required to:ï set up the driveï enter motor information.Code Description9901 LANGUAGESelects the display language. There are two different Assistant Control Panels, each supporting a different languageset. (Panel ACS-CP-L supporting languages 0, 2, 11Ö15 will be integrated into ACS-CP-A.)9902 APPLIC MACROSelects an application macro. Application macros automatically edit parameters to configure the ACS550 for aparticular application.31 = LOAD FD SET ñ FlashDrop parameter values as defined by the FlashDrop file. Parameter view is selected byparameter 1611 PARAMETER VIEW.ï FlashDrop is an optional device for fast copying of parameters to unpowered drives. FlashDrop allows easycustomization of the parameter list, e.g. selected parameters can be hidden. For more information, see MFDT-01FlashDrop Userís Manual [3AFE68591074 (English)].-1 = USER S1 SAVE, -3 = USER S2 SAVE ñ With these it is possible to save two different user parameter sets into thedrive permanent memory for later use. Each set contains parameter settings, including Group 99: START-UPDATA, and the results of the motor identification run.0 = USER S1 LOAD, -2 = USER S 2 LOAD ñ With these the user parameter sets can be taken back in use.9904 MOTOR CTRL MODESelects the motor control mode.1 = VECTOR :SPEED ñ sensorless vector control mode.ï Reference 1 is speed reference in rpm.ï Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002MAXIMUM SPEED, or 2001 MINIMUM SPEED if the absolute value of the minimum speed is greater than the maximumspeed).2 = VECTOR :TORQ.ï Reference 1 is speed reference in rpm.ï Reference 2 is torque reference in % (100% is nominal torque.)3 = SCALAR:FREQ ñ scalar control mode.ï Reference 1 is frequency reference in Hz.ï Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter2008 MAXIMUM FREQ , or 2007 MINIMUM FREQ if the absolute value of the minimum speed is greater than themaximum speed).9905 MOTOR NOM VOLTDefines the nominal motor voltage.ï Must equal the value on the motor rating plate.ï The ACS550 cannot supply the motor with a voltage greater than the input power (mains) voltage.Assistant Control Panel ACS-CP-A:Assistant Control Panel ACS-CP-D (Asia):0 = ENGLISH 1 = ENGLISH ( AM ) 2 = DEUTSCH 3 = ITALIANO 4 = ESPA—OL5 = PORTUGUES 6 = NEDERLANDS 7 = FRAN«AIS 8 = DANSK 9 = SUOMI10 = SVENSKA 11 = RUSSKI 12 = POLSKI 13 = T‹RK«E 14 = CZECH15 = MAGYAR0 = ENGLISH 1 = CHINESE 2 = KOREAN 3 = JAPANESE1 = ABB STANDARD 2 = 3- WIRE 3 = ALTERNATE 4 = MOTOR POT 5 = HAND/AUTO6 = PID CONTROL 7 = PFC CONTROL 8 = TORQUE CTRL 31 = LOAD FD SET0 = USER S 1 LOAD -1 = USER S 1 SAVE -2 = USER S 2 LOAD -3 = USER S 2 SAVE