12 EN – R6…R9 Quick installation guideR0-R4R6-R9R6-R9ENDADEESFIFRITNLPLPTRUSVTRZHFor information on reforming the capacitors, see Converter module capacitorreforming instructions (3BFE64059629 [English]), available on the Internet atwww.abb.com/drives/documents.Select the power cablesSize the power cables according to local regulations to carry the nominal currentgiven on the type designation label of your drive.Ensure the coolingSee table IEC ratings at UN = 230 V, 400 V and 480 V on page 7 for the losses. Theallowed operating temperature range of the drive is -15 to +50 °C (+5 to +122 °F). Nocondensation or frost is allowed. For more information on the ambient temperatureand derating, see chapter Technical data in ACS580-01 (0.75 to 250 kW, 1.0 to350 hp) hardware manual (3AXD50000044794 [English]).Protect the drive and input power cableSee tables gG fuses (on page 8) and uR or aR fuses (on page 9) for the fuses.If you use gG fuses, make sure that the operating time of the fuse is below0.5 seconds. Follow the local regulations.Install the drive on the wallWarning! The drive module is heavy (42 to 103 kg / 93 to 227 lb). Use asuitable lifting device. Do not lift the module manually. Make sure that the walland the fixing devices can carry the weight.Install the drive on the wallSee figure R6…R9 Figures A on page 31.Check the insulation of the power cables and the motorCheck the insulation of the input cable according to local regulations before connectingit to the drive.See figure B on page 31.1. Check the insulation of the motor cable and motor when the cable is disconnectedfrom the drive. Measure the insulation resistance between each phase conductorand then between each phase conductor and the Protective Earth conductorusing a measuring voltage of 1000 V DC. The insulation resistance of an ABB