Technical data83Technical dataWhat this chapter containsThis chapter contains the technical specifications of the drive, e.g. the ratings, sizesand technical requirements, provisions for fulfilling the requirements for CE andother markings, and warranty policy.IEC dataRatingsThe IEC ratings for the ACS800-04 with 50 Hz and 60 Hz supplies are given below.The symbols are described below the table.ACS800-04sizeNominal ratings No-overloaduseLight-overload use Heavy-duty use FramesizeAir flow HeatdissipationIcont.maxAImaxAPcont.maxkWI2NAPNkWI2hdAPhdkW m3/h WThree-phase supply voltage 208 V, 220 V, 230 V or 240 V-0080-2 214 326 55 211 55 170 45 R7 540 2900-0100-2 253 404 75 248 75 202 55 R7 540 3450-0120-2 295 432 90 290 90 240 4) 55 R7 540 4050-0140-2 405 588 110 396 110 316 90 R8 1220 5300-0170-2 447 588 132 440 132 340 90 R8 1220 6100-0210-2 528 588 160 516 160 370 110 R8 1220 6700-0230-2 613 840 160 598 160 480 132 R8 1220 7600-0260-2 693 1017 200 679 200 590 2) 160 R8 1220 7850-0300-2 720 1017 200 704 200 635 3) 200 R8 1220 8300Three-phase supply voltage 380 V, 400 V or 415 V-0140-3 206 326 110 202 110 163 90 R7 540 3000-0170-3 248 404 132 243 132 202 110 R7 540 3650-0210-3 289 432 160 284 160 240 1) 132 R7 540 4300-0260-3 445 588 200 440 200 340 160 R8 1220 6600-0320-3 521 588 250 516 250 370 200 R8 1220 7150-0400-3 602 840 315 590 315 477 250 R8 1220 8100-0440-3 693 1017 355 679 355 590 2) 315 R8 1220 8650-0490-3 720 1017 400 704 400 635 3) 355 R8 1220 9100