Start-up115ACS800-17LC-specific parameters in the IGBT Supply Control ProgramThe ACS800-17LC specific signals and parameters of IGBT Supply Control Programare described in the tables below.Terms and abbreviationsParametersTerm DefinitionB BooleanC Character stringDef. Default valueFbEq Fieldbus equivalent: the scaling between the value shown on the control panel and theinteger used in serial communicationI IntegerR RealT. Data type (see B, C, I, R)No. Name/Value Description T./FbEq Def.16 SYSTEM CTRINPUTSParameter lock, parameter back-up etc.16.15 START MODE Selects the start mode. B LEVELLEVEL Starts the supply unit by the level of digital input DI2. The supplyunit starts to modulate and the charging resistors will be by-passedwhen the supply unit RMIO board is powered, its digital input DI2 isON and there are no faults.0EDGE Starts converter by EDGE of control command. Control commandis selected by parameters 98.01 COMMAND SEL and 98.02COMM. MODULE.131 AUTOMATICRESETAutomatic fault reset.Automatic resets are possible only for certain fault types and whenthe automatic reset function is activated for that fault type.The automatic reset function does not operate if the drive is in localcontrol (L visible on the first row of the control panel display).WARNING! If the start command is selected and it is ON,the supply unit may restart immediately after automaticfault reset. Ensure that the use of this feature will notcause danger.WARNING! Do not use these parameters when the driveis connected to a common DC bus. The charging resistorsmay be damaged in an automatic reset.31.01 NUMBER OF TRIALS Defines the number of automatic fault resets the drive performswithin the time defined by parameter 31.02.I 00 … 5 Number of the automatic resets 031.02 TRIAL TIME Defines the time for the automatic fault reset function. Seeparameter 31.01.R 30 s1.0 … 180.0 s Allowed resetting time 100 …18000