Connecting the motor cablesRefer to the drawings below.WARNING!Obey the instructions in chapter Safety instructions. If you ignore them,injury or death, or damage to the equipment can occur.1. Do the steps in section Electrical safety precautions (page 19) before you start the work.2. Remove the shroud in front of the output busbars.3. For 360° grounding of the shield at the cable entry, remove the outer jacket of eachcable where they pass through the cable entry (a).4. Cut the cable to suitable length and strip the ends of the individual conductors. Twistthe shield strands together to form a separate conductor and wrap it with tape.5. Crimp suitable lug terminals onto the phase conductors and the ground conductor. Thedimensions of the output busbars are shown in chapter Technical data.6. Connect the phase conductors of the motor cable to the U2, V2 and W2 terminals. Youcan temporarily remove the plastic insulators (b) between the busbars to make theconnecting work easier.WARNING!The plastic insulators (b) between the busbars must be in place when theinverter is powered.7. Connect the shield (and any grounding conductors) of the cable to the PE busbar closeto the cable entries.8. Secure the cable mechanically.9. Repeat the procedure for each motor cable.10. Refit the shroud removed earlier.11. At the motor, connect the cables according to instructions from the motor manufacturer.Pay special attention to the phase order. For minimum radio-frequency interference,ground the cable shield 360 degrees at the cable entry of the motor terminal box, orground the cable by twisting the shield so that the flattened shield is wider than 1/5 ofits length.Electrical installation 117