Parameter Values (Range) Unit Step Default DescriptionAmplitude corr. A 0.900...1.100 0.001 1.000 Phase A Voltagephasor magnitudecorrection of anexternal voltagetransformerAmplitude corr. B 0.900...1.100 0.001 1.000 Phase B Voltagephasor magnitudecorrection of anexternal voltagetransformerAmplitude corr. C 0.900...1.100 0.001 1.000 Phase C Voltagephasor magnitudecorrection of anexternal voltagetransformerTable 26:Analog channel settings, residual voltageParameter Values (Range) Unit Step Default DescriptionSecondary voltage 1=100V2=110V3=115V4=120V1=100V Secondary voltagePrimary voltage 0.001...440.000 kV 0.001 11.547 Primary voltageAmplitude corr. 0.900...1.100 0.001 1.000 Amplitude correctionTable 27:Alarm LED input signalsName Type Default DescriptionAlarm LED 1 BOOLEAN 0=False Status of Alarm LED 1Alarm LED 2 BOOLEAN 0=False Status of Alarm LED 2Alarm LED 3 BOOLEAN 0=False Status of Alarm LED 3Alarm LED 4 BOOLEAN 0=False Status of Alarm LED 4Alarm LED 5 BOOLEAN 0=False Status of Alarm LED 5Alarm LED 6 BOOLEAN 0=False Status of Alarm LED 6Alarm LED 7 BOOLEAN 0=False Status of Alarm LED 7Alarm LED 8 BOOLEAN 0=False Status of Alarm LED 8Alarm LED 9 BOOLEAN 0=False Status of Alarm LED 9Alarm LED 10 BOOLEAN 0=False Status of Alarm LED 10Alarm LED 11 BOOLEAN 0=False Status of Alarm LED 11Section 4 1MRS756378 DBasic functions112 REF615Application Manual