Table 31:Ethernet front port settingsParameter Values (Range) Unit Step Default DescriptionIP address 192.168.000.254 IP address for front port (fixed)Mac address XX-XX-XX-XX-XX-XXMac address for front portTable 32:Ethernet rear port settingsParameter Values (Range) Unit Step Default DescriptionIP address 192.168.002.010 IP address for rear port(s)Subnet mask 255.255.255.000 Subnet mask for rear port(s)Default gateway 192.168.002.001 Default gateway for rear port(s)Mac address XX-XX-XX-XX-XX-XXMac address for rear port(s)Table 33:General system settingsParameter Values (Range) Unit Step Default DescriptionRated frequency 1=50Hz2=60Hz1=50Hz Rated frequency of the networkPhase rotation 1=ABC2=ACB1=ABC Phase rotation orderBlocking mode 1=Freeze timer2=Block all3=Block OPERATEoutput1=Freeze timer Behaviour for function BLOCK inputsBay name REF615 Bay name in systemSG follow input 0=False1=True0=False Enable setting group change to follow the inputstateTable 34:HMI settingsParameter Values (Range) Unit Step Default DescriptionFB naming convention 1=IEC618502=IEC606173=IEC-ANSI1=IEC61850 FB naming convention used in IEDDefault view 1=Measurements2=Main menu1=Measurements LHMI default viewBacklight timeout 1...60 min 1 3 LHMI backlight timeoutWeb HMI mode 1=Active read only2=Active3=Disabled3=Disabled Web HMI functionalityWeb HMI timeout 1...60 min 1 3 Web HMI login timeout1MRS756378 D Section 4Basic functionsREF615 115Application Manual