• Only such CBBs that are set for the next shot in the sequence can be acceptedfor execution. For example, if the next shot in the sequence should be shot 2, arequest from CBB set for shot 3 is rejected.• Any CBB that is set for the next shot or any of the following shots can be acceptedfor execution. For example, if the next shot in the sequence should be shot 2, alsoCBBs that are set for shots 3, 4 and 5 are accepted. In other words, shot 2 can beignored.In case there are multiple CBBs allowed for execution, the CBB with the smallestnumber is chosen. For example, if CBB2 and CBB4 request an execution, CBB2 isallowed to execute the shot.The auto-reclose function can perform up to five auto-reclose shots or cycles.10.4.3.3 Configuration examplesA070886 V2 ENFigure 108: Example connection between protection and auto-reclose functionsin IED configurationIt is possible to create several sequences for a configuration.Auto-reclose sequences for overcurrent and non-directional earth-fault protectionapplications where high speed and delayed auto-reclosings are needed can be asfollows:Section 10 1MRS756378 DControl functions218 REF615Application Manual