Function status earth-fault for IEC 60870-5-103 I103EFI103EF is a function block with defined functions for earthfault indications in monitor direction. This block includes theFunctionType parameter; theinformation number parameteris defined for each output signal.Function status fault protection for IEC 60870-5-103I103FLTPROTI103FLTPROT is used for fault indications in monitordirection. Each input on the function block is specific for acertain fault type and therefore must be connected to acorrespondent signal present in the configuration. Forexample: 68_TRGEN represents the General Trip of thedevice and must be connected to the general trip signalSMPPTRC_TRIP or equivalent.IED status for IEC 60870-5-103 I103IEDI103IED is a function block with defined IED functions inmonitor direction. This block uses the parameterFunctionType; theinformation number parameter is definedfor each input signal.Supervison status for IEC 60870-5-103 I103SUPERVI103SUPERV is a function block with defined functions forsupervision indications in monitor direction. This blockincludes theFunctionType parameter; theinformation numberparameter is defined for each output signal.Status for user-defined signals for IEC 60870-5-103I103USRDEFI103USRDEF comprises function blocks with user-definedinput signals in monitor direction. These function blocksinclude theFunctionType parameter for each block in theprivate range, and theinformation number parameter for eachinput signal.Function commands for IEC 60870-5-103 I103CMDI103CMD is a command function block in control directionwith pre-defined output signals. The signals are in steadystate, not pulsed, and stored in the IED in case of restart.IED commands for IEC 60870-5-103 I103IEDCMDI103IEDCMD is a command block in control direction withdefined IED functions. All outputs are pulsed and they areNOT stored. Pulse-time is a hidden parameter.Function commands user-defined for IEC 60870-5-103I103USRCMDI103USRCMD is a command block in control direction withuser-defined output signals. These function blocks includetheFunctionType parameter for each block in the privaterange, and theInformation number parameter for each outputsignal.Function commands generic for IEC 60870-5-103I103GENCMDI103GENCMD is used for transmitting generic commandsover IEC 60870-5-103. The function has two output signals,CMD_OFF and CMD_ON, that can be used to implementdouble-point command schemes.The I103GENCMD component can be configured as either 2pulsed ON/OFF or 2 steady ON/OFF outputs. The ON outputis pulsed with a command with value 2, while the OFF outputis pulsed with a command with value 1. If in steady mode isON asserted and OFF deasserted with command 2 and viceversa with command 1.IED commands with position and select for IEC 60870-5-103I103POSCMDI103POSCMD has double-point position indicators that aregetting the position value as an integer (for example, from thePOSITION output of the SCSWI function block) and sending itover IEC 60870-5-103 (1=OPEN; 2=CLOSE). The standarddoes not define the use of values 0 and 3. However, whenconnected to a switching device, these values aretransmitted.The BLOCK input will block only the signals in monitoringdirection (the position information), not the commands via IEC60870-5-103. The SELECT input is used to indicate that themonitored apparatus has been selected (in a select-before-operate type of control).DNP3.0 communication protocol SEMOD153688-5 v3An electrical RS485 serial port, optical serial ports on theserial communication module (SLM), optical Ethernet portsare available for DNP3.0 communication. DNP3.0 Level 2communication with unsolicited events, time synchronizationand disturbance reporting is provided for communication toRTUs, Gateways or HMI systems.Multiple command and transmit M14791-3 v3When IEDs are used in Substation Automation systems withLON, SPA or IEC 60870-5-103 communication protocols, theEvent and Multiple Command function blocks are used as thecommunication interface for vertical communication to stationHMI and gateway, and as interface for horizontal peer-to-peercommunication (over LON only).17. Hardware descriptionHardware modules IP14529-1 v1Numeric processing module NUM M12643-3 v3The numeric processing module (NUM) is a CPU module thathandles all protection functions and logic.NUM provides up to 4 optical (type LC) or galvanic (typeRJ45) Ethernet ports(one basic and three optional).Power supply module PSM M11595-3 v6The power supply module is used to provide the correctinternal voltages and full isolation between the IED and thebattery system. An internal fail alarm output is available.1MRK 506 384-BEN ALine distance protection REL650 2.2Product version: 2.2.128 ABB