11.4.7.2 Function block M13500-3 v5SXCBRBLOCKLR_SWIOPENCLOSEBL_OPENBL_CLOSEBL_UPDPOSOP ENPOSCLOSECBOPCAPTR_OPENTR_CLOSERS_CNTEEH_WARNEEH_ALMXIN*XPOSEXE_OPEXE_CLOP_BLKDCL_BLKDUPD_BLKDOPENP OSCLOSEPOSTR_POSCNT_VALL_CAUSEEEHEALTHCBOPCAPIEC05000338-4-en.vsdxIEC05000338 V5 EN-USFigure 203: SXCBR function block11.4.7.3 SignalsPID-6799-INPUTSIGNALS v2Table 223:SXCBR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionLR_SWI BOOLEAN 0 Local/Remote switch indication from switchyardOPEN BOOLEAN 0 Pulsed signal used to immediately open theswitchCLOSE BOOLEAN 0 Pulsed signal used to immediately close theswitchBL_OPEN BOOLEAN 0 Signal to block the open commandBL_CLOSE BOOLEAN 0 Signal to block the close commandBL_UPD BOOLEAN 0 Steady signal for block of the position updatingPOSOPEN BOOLEAN 0 Signal for open position of apparatus from I/OPOSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/OCBOPCAP INTEGER 3 Breaker operating capability 1 = None, 2 = O, 3 =CO, 4 = OCO, 5 = COCO, 6+ = MoreTR_OPEN BOOLEAN 0 Signal for open position of truck from I/OTR_CLOSE BOOLEAN 0 Signal for close position of truck from I/ORS_CNT BOOLEAN 0 Resets the operation counterEEH_WARN BOOLEAN 0 Warning from external equipmentEEH_ALM BOOLEAN 0 Alarm from external equipmentXIN GROUPSIGNAL- Execution information from CSWISection 11 1MRK 506 382-UEN AControl404 Line distance protection REL650 2.2 IECTechnical manual