PID-6828-INPUTSIGNALS v3Table 489:GOOSEDPRCV Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionSRCDPOUT INTEGER 0 Source to double point outputPID-6828-OUTPUTSIGNALS v3Table 490:GOOSEDPRCV Output signalsName Type DescriptionDPOUT INTEGER Double point outputDATAVALID BOOLEAN Data valid for double point outputCOMMVALID BOOLEAN Communication valid for double point outputTEST BOOLEAN Test output17.4.7.5 SettingsPID-6828-SETTINGS v3Table 491:GOOSEDPRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/On17.4.7.6 Operation principle GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v4The DATAVALID output will be HIGH if the incoming message is with valid data.The COMMVALID output will become LOW when the sending IED is under totalfailure condition and the GOOSE transmission from the sending IED does nothappen.The TEST output will go HIGH if the sending IED is in test mode.Data Value Data Valid Comm Valid TestIncoming data with q=Normal Updated 1 1 0Incoming data with q=oldData 0 0 1 0Incoming data with q=Invalid 0 0 1 0Incoming data with q=test 0 0 1 1Incoming data with q=test+oldData 0 0 1 1Receiver in block 0 0 1 0Receiver in block andcommunication error0 0 0 0Table continues on next pageSection 17 1MRK 506 382-UEN AStation communication680 Line distance protection REL650 2.2 IECTechnical manual