that are recorded are available for transfer to the master. A file that has been transferred andacknowledged by the master cannot be transferred again.• The binary signals that are included in the disturbance recorder are those that are connectedto the disturbance function blocks B1RBDR to B6RBDR. These function blocks include thefunction type and the information number for each signal. For more information on thedescription of the Disturbance report in the Technical reference manual. The analog channels,that are reported, are those connected to the disturbance function blocks A1RADR to A4RADR.The eight first ones belong to the public range and the remaining ones to the private range.Settings M17109-116 v1Settings for RS485 and optical serial communication M17109-118 v10General settingsSPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical serial port whileDNP and IEC 60870-5-103 only can utilize the RS485 port. A single protocol can be active on a givenphysical port at any time.Two different areas in the HMI are used to configure the IEC 60870-5-103 protocol.1. The port specific IEC 60870-5-103 protocol parameters are configured under:Main menu/Configuration/Communication/Station Communication/IEC6870-5-103/• • SlaveAddress• BaudRate• RevPolarity (optical channel only)• CycMeasRepTime• MasterTimeDomain• TimeSyncMode• EvalTimeAccuracy• EventRepMode• CmdMode• RepIntermediatePos is:• “OPTICAL103:1” for the optical serial channel on the SLM• “RS485103:1” for the RS485 port2. The protocol to activate on a physical port is selected under:Main menu/Configuration/Communication/Station Communication/Port configuration/• RS485 port• RS485PROT:1 (off, DNP, IEC103)• SLM optical serial port• PROTOCOL:1 (off, DNP, IEC103, SPA)Section 18 1MRK 511 364-UUS AStation communication270Application manual