134.Appli c ati onREU 610 is a versatile multifunction voltage relay which is used in generalvoltage supervision applications. It complements the range of feederprotection relay R E F 610 and motor protection relay R E M 610 in industrialoutgoing feeder and motor feeder applications. The relay can also be used asback- up protection for industrial as well as utility applications.The large number of integrated protection functions, including two- stageovervoltage protection, two- stage undervoltage protection and two- stageresidual overvoltage protection, makes the relay a complete protection againstvarious voltage fault conditions.The large number of digital inputs and output contacts allows a wide range ofapplications.4.1. Req u i r em en tsTo secure correct and safe operation of the relay, preventive maintenance isrecommended to be performed every five years when the relay is operatingunder the specified conditions; see Table 4 .1.- 1 andSection 5 .2.3 . Technical data.When being used for real- time clock or recorded data functions, the batteryshould be changed every five years.Table 4.1.-1 Env ironmental conditionsRecommended temperature range ( continuous) -10...+ 55°CLimit temperature range ( short-term) -40...+ 70°CTemperature influence on the operation accuracy of the voltagerelay w ithin the specified service temperature range0.1% / °CTransport and storage temperature range -40...+ 85°C4.2.Con f i gu r ati onThe appropriate configuration of the output contact matrix enables the use ofthe signals from the protection stages as contact functions. The start signalscan be used for blocking co- operating protection relays and signalling.The F ig. 4 .2.- 1 represents the relay with the default configuration: all startsignals are routed to signal outputs and all trip signals to power outputs.1MRS755769 Voltage RelayTechnical Reference ManualREU 610