Section 6 Operating procedures6.1 Monitoring6.1.1 IndicationsThe operation of the IED can be monitored via three different indications on theLHMI.• Three indicator LEDs with fixed functionality: Ready, Start and Trip• 15 programmable three-color alarm LEDs which can present 45 virtual LEDstates• Texts which are shown on the alarm view can be programmed for each LEDcolour and off state. Programming can be done with PCM600, via WHMIand LHMI. These texts are displayed on the LHMI.• An auto-indicating message on the display.6.1.1.1 Using auto-indication messagesAuto-indication messages are shown in a dialog box that is displayed when thedisturbance recorder is triggered. The indication dialog box shows a list of currentdisturbance recordings one by one. To scroll the dialog, use and .To activate the auto-indication message function, the disturbancerecorder function has to be activated and properly configured. Checkalso that the setting Main menu/Configuration/HMI/LHMI/AutoIndicationDRP is set to “On”.1. Read the auto-indication message in the dialog box.The message contains the same information that is available for disturbancerecordings.2. Press to see more detailed information.3. Press to close the auto-indication message without clearing it or press toactivate the Clear view and to clear messages.1MRS756509 E Section 6Operating procedures630 series 65Operation Manual