Name Type DescriptionSTHDTL3 BOOLEAN Start signal for harmonic over load DT stage ofphase L3STHIDML1 BOOLEAN Start signal for harmonic over load IDMT stage ofphase L1STHIDML2 BOOLEAN Start signal for harmonic over load IDMT stage ofphase L2STHIDML3 BOOLEAN Start signal for harmonic over load IDMT stage ofphase L3RECNINH BOOLEAN Capacitor bank reconnection inhibit signal6.8.5 Setting parametersTable 130:CBPGAPC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OnIBase 1 - 99999 A 1 3000 Rated capacitor bank currentOperationRecIn OffOn- - On Operation reconnection inhibit Off/OnIRecnInhibit< 4 - 1000 %IB 1 10 Cap bank cut off current level for inhibitin % of IBasetReconnInhibit 1.00 - 6000.00 s 0.01 300.00 Time delay for reconnected inhibit signalOperationOC OffOn- - On Operation over current Off/OnIOC> 0 - 900 %IB 1 135 Start level for over current operation, %of IBasetOC 0.00 - 6000.00 s 0.01 30.00 Time delay for over current operationOperationUC OffOn- - Off Operation under current Off/OnIUC< 5 - 100 %IB 1 70 Start level for under current operation, %of IBasetUC 0.00 - 6000.00 s 0.01 5.00 Time delay for under current operationOperationQOL OffOn- - On Operation reactive power over load Off/OnQOL> 5 - 900 % 1 130 Start level for reactive power over load in%tQOL 1.00 - 6000.00 s 0.01 60.00 Time delay for reactive power overloadoperationOperationHOL OffOn- - On Operation harmonic over load Off/OnHOLDTU> 5 - 500 % 1 200 Start value of voltage for harmOvLoadfor DT stage in %tHOLDT 0.00 - 6000.00 s 0.01 10.00 Time delay for minimum operation forharmonic overloadHOLIDMTU> 80 - 200 % 1 110 Start value of voltage for harmOvLoad inIDMT stage in %Table continues on next pageSection 6 1MRK 505 208-UEN BCurrent protection210Technical reference manual