Name Type DescriptionPOS2 BOOLEAN Position 2 indication, logical signalCMDPOS12 BOOLEAN Execute command from position 1 to position 2CMDPOS21 BOOLEAN Execute command from position 2 to position 111.5.5 Setting parametersTable 246:VSGGIO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnCtlModel Dir NormSBO Enh- - Dir Norm Specifies the type for control modelaccording to IEC 61850Mode SteadyPulsed- - Pulsed Operation modetSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and executesignalstPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght11.6 Single point generic control 8 signals SPC8GGIOFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSingle point generic control 8 signals SPC8GGIO - -11.6.1 IntroductionThe Single point generic control 8 signals (SPC8GGIO) function block is acollection of 8 single point commands, designed to bring in commands fromREMOTE (SCADA) to those parts of the logic configuration that do not needextensive command receiving functionality (for example, SCSWI). In this way,simple commands can be sent directly to the IED outputs, without confirmation.Confirmation (status) of the result of the commands is supposed to be achieved byother means, such as binary inputs and SPGGIO function blocks. The commandscan be pulsed or steady.11.6.2 Principle of operationThe PSTO input will determine which the allowed position for the operator(LOCAL, REMOTE, ALL) is. Upon sending a command from an allowed operatorposition, one of the 8 outputs will be activated. The settings Latchedx and tPulsex(where x is the respective output) will determine if the signal will be pulsed (and1MRK 505 208-UEN B Section 11Control423Technical reference manual