Name Values (Range) Unit Step Default DescriptiontPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse duration, in [s]tDelay 0.000 - 60000.000 s 0.010 0.000 Time delay on the output, in [s]StopAtExtremes DisabledEnabled- - Disabled Stop when min or max position is reached11.5 Selector mini switch VSGGIOFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSelector mini switch VSGGIO - -11.5.1 IntroductionThe Selector mini switch VSGGIO function block is a multipurpose function usedfor a variety of applications, as a general purpose switch.VSGGIO can be controlled from the menu or from a symbol on the single linediagram (SLD) on the local HMI.11.5.2 Principle of operationSelector mini switch (VSGGIO) function can be used for double purpose, in thesame way as switch controller (SCSWI) functions are used:• for indication on the single line diagram (SLD). Position is received throughthe IPOS1 and IPOS2 inputs and distributed in the configuration through thePOS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.• for commands that are received via the local HMI or IEC 61850 anddistributed in the configuration through outputs CMDPOS12 and CMDPOS21.The output CMDPOS12 is set when the function receives a CLOSE commandfrom the local HMI when the SLD is displayed and the object is chosen.The output CMDPOS21 is set when the function receives an OPEN commandfrom the local HMI when the SLD is displayed and the object is chosen.It is important for indication in the SLD that the a symbol isassociated with a controllable object, otherwise the symbol won't bedisplayed on the screen. A symbol is created and configured inGDE tool in PCM600.The PSTO input is connected to the Local remote switch to have a selection ofoperators place , operation from local HMI (Local) or through IEC 618501MRK 505 208-UEN B Section 11Control421Technical reference manual