15.13.4 Setting example GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v1For absolute comparison between inputs:Set theEnaAbs =1Set theRefSource =1Similarly for Signed comparison between inputsSet theEnaAbs =0Set theRefSource =1For absolute comparison between input and settingSet theEnaAbs =1Set theRefSource =0SetValue shall be set between -2000000000 to 2000000000Similarly for signed comparison between input and settingSet theEnaAbs =0Set theRefSource =0SetValue shall be set between -2000000000 to 2000000000.15.14 Comparator for real inputs - REALCOMP15.14.1 Identification GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberComparator for real inputs REALCOMP Real<=>15.14.2 Application GUID-5F7B1683-9799-4D27-B333-B184F8861A5B v1The function gives the possibility to monitor the level of real values in the system relative toeach other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,supervision, interlocking and other logics.15.14.3 Setting guidelines GUID-DE69FF5B-7D34-4A30-9060-214E98BFF798 v1Setting procedure on the IED:EnaAbs: This setting is used to select the comparison type between signed and absolutevalues.•Absolute: The function will do absolute comparison between input and reference value.•Signed: The function will do signed comparison between input and reference value.Section 15 1MRK 511 358-UEN ALogic372Application manual