Section 17 Metering17.1 Pulse-counter logic PCFCNT IP14600-1 v317.1.1 IdentificationM14879-1 v4Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberPulse-counter logic PCFCNTS00947 V1 EN-US-17.1.2 Application M13395-3 v6Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for instancepulses coming from an external energy meter, for calculation of energy consumption values.The pulses are captured by the binary input module (BIM), and read by the PCFCNT function.The number of pulses in the counter is then reported via the station bus to the substationautomation system or read via the station monitoring system as a service value. When usingIEC 61850–8–1, a scaled service value is available over the station bus.The normal use for this function is the counting of energy pulses from external energy meters.An optional number of inputs from an arbitrary input module in IED can be used for thispurpose with a frequency of up to 40 Hz. The pulse-counter logic PCFCNT can also be used as ageneral purpose counter.17.1.3 Setting guidelines M13396-4 v9Parameters that can be set individually for each pulse counter from PCM600:•Operation:Off/On•tReporting:0-3600s•EventMask:NoEvents/ReportEventsConfiguration of inputs and outputs of PCFCNT is made via PCM600.On the Binary input module (BIM), the debounce filter default time is set to 1 ms, that is, thecounter suppresses pulses with a pulse length less than 1 ms. The input oscillation blockingfrequency is preset to 40 Hz meaning that the counter detects the input to oscillate if theinput frequency is greater than 40 Hz. Oscillation suppression is released at 30 Hz. Block/release values for oscillation can be changed on the local HMI and PCM600 under Main menu/Configuration/I/O modules.1MRK 511 358-UEN A Section 17Metering401Application manual