ABB | SACE Emax 2184 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A Electronic accessories | 3 - Ekip Measuring modulesContinued from the previous pageThe following table shows the configuration parameters of the modules:Parameter Values Default DescriptionVoltageTransf. Absent, Present Absent• Absent = Isolation transformer onthe supply side of the inputs of themodule is absent.• Present = Isolation transformer onthe supply side of the inputs of themodule is present.Rated voltage100 V, 115 V, 120 V, 190 V, 208 V,220 V, 230 V, 240 V, 277 V, 347 V,380 V, 400 V, 415 V, 440 V, 480 V,500 V, 550 V, 600 V, 660 V, 690 V400 VDisplayed with "Voltage Transf." setas absent: the rated voltage of theinstallation.Primaryvoltage100 V, 115 V, 120 V, 190 V, 208 V,220 V, 230 V, 240 V, 277 V, 347 V,380 V, 400 V, 415 V, 440 V, 480 V,500 V, 550 V, 600 V, 660 V, 690 V,910 V, 950 V, 1000 V, 1150 V400 VDisplayed with "Voltage Transf." setas present: the primary voltage ofthe isolation transformer.Secondaryvoltage100 V, 110 V, 115 V, 120 V, 200 V,230 V 100 VDisplayed with "Voltage Transf." setas present: the secondary voltage ofthe isolation transformer.Power flow Bottom->Top, Top->Bottom Low->High• Bottom->Top = Flow of powerfrom the low terminals to the highterminals of the circuit-breaker (loadconnected to top).• Top->Bottom = Flow of powerfrom the high terminals to the lowterminals the circuit-breaker (loadconnected to bottom).Neutralconnection Absent, Present Present• Present = It enables measurementof the phase voltages.• Absent = It disables measurementof the phase voltages (only itenables measurement of line-to-linevoltages).The following table shows the path from the display to get information on the modules:AboutProtection UnitCircuit-breakerModules…Ekip Measuring…Power ControllerThe items of information on the modules that can be displayed are the serial number and the version ("Basic"in the case of Ekip Measuring, "Pro" in the case of Ekip Measuring Pro).SignallingsAThe following table shows the possible signals, and their meaning:Pos. DescriptionAPower status LED, green; present only on the Ekip Measuring Pro. The possible states are:• Off: the power supplied by the Ekip Measuring Pro to the trip unit is absent.• On fixed: the power supplied by the Ekip Measuring Pro to the trip unit is present.