ABB | SACE Emax 2Ekip Touch protection trip unit | 6 - Menu51 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. AAbout Menu This menu allows you to view information on:• Mainboard and trip unit (serial number, model, software version, etc.).• The circuit-breaker (serial number, rated current, configuration with or without neutral, number of poles,fixed or withdrawable version, state, etc).• The connected electronic accessories (serial number, model if present, software version if present,information on state if present, etc).• Date and time.InformationFunctionProtection unitIt displays:• Information on Mainboard and trip unit.• Date and time.Circuit Breaker Displays information on the circuit-breaker.Modules It displays a list of the electronic accessories connected.Power Controller (1) • Load input status: shows the Open/Closed state of the loads• Load Active: shows the Active/Inactive state of the loads.(1) Menus available with the Power Controller function enabled (see the Settings Menu- Power Controller).Measurements Menu This menu allows you to:• It open lists of recorded events.• It display measurements in graphical or numerical form.• It reset measurements.The following table shows the submenus and the parameters associated to the menu Measurements upto Level 3 (if present), and the Ekip Touch trip units where they can be found. The options correspondingto parameters and commands are underlined, to distinguish them from those corresponding to submenus.MeasurementsOptions Trip unitsHistoricals• Trip: it opens a list of the trip performed.• Events: it opens a list of the recorded events.• Measurements: it opens a list of the dimensions whose history canbe displayed.TouchG-TouchHi-TouchG Hi-TouchPower factor It displays the power factor measured.Touch (1)G-TouchHi-TouchG Hi-TouchFrequency It shows the frequency measured for the voltages.Energy• Energy counters: it displays the active, reactive and apparentenergies measured.• Reset counters: it resets the energy counters.• Energy RESET: opens a list of the parameters for programming thereset of the energy counters (see the chapter "20 - Operating features",and the paragraph "Functional characteristics", on page 124).Peak factor It shows the peak factors measured for the phase currents and theneutral currents.TouchG-TouchHi-TouchG Hi-TouchHarmonicDistortionIt opens the Modify Parameters page, to enable/disable the alarmwith a peak factor greater than 2.1.EkipSynchrocheck (2)It opens a list of the measurements related to the synchronismfunction.Touch (1)G-TouchHi-TouchG Hi-TouchNetworkAnalyzer (3)• V Sequences: it shows the last and penultimate positive andnegative voltage sequences measured.• V 3s Sequences: it shows the voltage sequences and unbalancemeasured in last the 3 seconds.• THD Current: it shows the measurements of the harmonicdistortion of currents.• THD Voltages: it shows the measurements of the harmonicdistortion of line-to-line voltages.• Counters: it allows you to display the number of events monitoredby the function in the last twenty-four hours and the totals.• Waveforms: it opens a list of the currents and voltages for which aninstantaneous wave form can be displayed.Hi-TouchG Hi-TouchContinued on the next page