Description of application and parametersApplication "1-button switching"KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905 │2510.3 Application "1-button switching"NOTEThe application is valid for the following parts of the device:■ Button 1 / rocker 1■ Button 2■ Button 3 / rocker 2■ Button 4When actuated or released a switching telegram is sent out. In each case, the applicationmakes a separate set of parameters and communication objects available for the 1st and the2nd button. The other side of the button can be assigned a further "button-oriented" function.10.3.1 General parameters - Reaction on rising edgeOptions: OnOffAlternating on/offDeactivatedThe application can differentiate between the operation and the releasing of the button. Anoperation is designated as "Rising edge" and the releasing is designated as "Falling edge".The application "1-button switching" makes two separate "Switching" communication objectsavailable for the left or right side of the button. The value 1 is always sent out on the first object(Value 1) and the value 2 is always sent out on the second object (Value 2).The "Reaction to rising edge" parameter specifies whether the "Value 1 for rising edge" or the"Value 2 for rising edge" is sent out for rising edge.Alternatively, Value1/Value2 can also be alternatingly set for a rising edge, i.e. after Value 1was sent (or received), a renewed operation will send out Value 2. After it is operated again,Value 1 is again sent out.The values 1 and 2 are specified via the parameters "Value 1 for rising edge" and "Value 2".The "Deactivated" setting causes no telegram to be sent out for an operation of the button.