A new recording begins. The view is updated if you leave the menu andreturn.1.2. Navigate to General information or to Trip values to obtain more detailedinformation.2. Open the Disturbance handling tool for the IED in the plant structure in PCM600.2.1. Right-click and select Execute manual Trig in the window Availablerecordings in IED.2.2. Read the required recordings from the IED.2.3. Refresh the window Recordings and select a recording.2.4. Right-click and select Create Report or Open With to export the recordingsto any disturbance analyzing tool that can handle Comtrade formatted files.Evaluation of the results from the disturbance recording function requires access to aPC either permanently connected to the IED or temporarily connected to the Ethernetport (RJ-45) on the front. The PCM600 software package must be installed in the PC.Disturbance upload can be performed by the use of PCM600 or by any third party toolwith IEC 61850 protocol. Reports can automatically be generated from PCM600.Disturbance files can be analyzed by any tool reading Comtrade formatteddisturbance files.It could be useful to have a printer for hard copies. The correct start criteria andbehavior of the disturbance recording function can be checked when IED protectivefunctions are tested.When the IED is brought into normal service it is recommended to delete allrecordings, made during commissioning to avoid confusion in future fault analysis.All recordings in the IED can be deleted in two ways:1. in the local HMI under Main menu/Clear/Reset disturbances, or2. in the Disturbance handling tool in PCM600 by selecting Delete all recordings inthe IED... in the window Available Recordings in IED.10.1.4 Event recorder (ER) and Event list (EL)The result from the event recorder and event list can be viewed on the local HMI or,after upload, in PCM600 as follows:1. on the local HMI under Main menu/Events, or in more details via2. the Event Viewer in PCM600.The internal FIFO register of all events will appear when the event viewer islaunched.When the IED is brought into normal service it is recommended to delete all eventsresulting from commissioning tests to avoid confusion in future fault analysis. Allevents in the IED can be cleared in the local HMI under Main Menu//Clear/ClearSection 10 1MRK 511 360-UEN ATesting functionality by secondary injection84 Bay control REC670 2.1 IECCommissioning manual