36 Power Quality Analyzer Model 82305.3.3 Apparent Power (VA)02/25/0649.99Hz 10:26V A VA V -,+ A -,+123100.0 %VAh01min 100.0 %+030 °max 100.0 %100-100%01 3 5 7 9 11 13 15 17 19 21 23 25Figure 5-12ITEM FUNCTION1. This information concerns the harmonic located under the cursor.VAh xx: Number of the harmonic.%: Level of the harmonic with respect to the fundamental (order 1).+030: Phase shift of the voltage harmonic with respect to the current harmonicfor the order in question.Max/Min: Indicators of the maximum and minimum of the level of the harmonic inquestion (reset at each change of harmonic number).2. The horizontal axis indicates the orders of the harmonics.(the bars of the chart that are above the horizontal axis represent harmonic powerconsumed, while those below it represent harmonic power generated).Display of the levels of the harmonics as a percentage with respect to the fundamen-tal (order 1).Order 0: DC component (with MR193 only)Order (1 to 25): order of the harmonics. As soon as the cursor goes past order 25, therange from 26 to 50 appears.Note: The ► icon to the right of harmonic 25 indicates the presence of harmonics oforder higher than 25.3. Analysis of the apparent power harmonics**Not available with a balanced three-phase connection.