www.advancedco.com264.2.3.2 ActionTo change the action, press the ✔ button and a further menu with options is shown.[Input Action] ↓NOT IN USETRANSMIT –ONCETRANSMIT – REPEATTEST MODETEST OVERRIDEThe menu shows the input actions available.The following input actions are possible:Action FunctionNOT IN USE This input is not usedTRANSMIT – ONCE Activation of this input will result in the input text defined for this input being sent once (or the minimum number ofsends allowed – see section 4.2.7 for details).TRANSMIT – REPEAT Activation of this input will result in the input text defined for this input being sent continuously while ever the inputremains active, with an interval of 10 seconds.TEST MODE Activation of this input will place the panel into TEST mode (alternative method to the key-switch and menufunctions). Note: ENGINEER mode overrides TEST mode.TEST OVERRIDE Activation of this input will cause any active test-mode to be cancelled. This is intended to cover a situation wherea real fire occurs whilst part of the system is undergoing testing.GENERAL FAULT Activation of this input will place the panel into a fault condition.LEVEL-2 ACCESS Activation of this input will enable Level-2 control and menu functions (alternative method to the key-switch andmenu functions). All such inputs (and key-switch) must be inactive in order to cancel level-2 access.ENGINEER MODE Activation of this input will place the panel into ENGINEER mode (alternative method to the key-switch and menufunctions). Note: ENGINEER mode overrides TEST mode.WALK TEST Activates a special sequence which transmits a test message repeatedly (time interval dependant onconfiguration) to allow a one-man walk test of the building to assist in ascertaining reception coverage.4.2.3.3 MonitoredThe switch wiring can be set to monitored (Yes) or not monitored (No).When set to monitored, the panel will check the wiring for normal, open circuit, short circuit and activeconditions.When set to not monitored, the panel will check for normal and activation only.To change the monitored parameter, press the ✔ button to toggle between YES and NO.4.2.3.4 Type:The normal input condition can be changed to suit the type of switch connected.To change the type parameter, press the ✔ button to toggle between NORMALLY OPEN and NORMALLYCLOSED.The default setting is normally open.4.2.3.5 Pager Group:The Pager Group setting determines which pagers in use on site the message will be sent to. The number ofpager groups actually available will be dependant on the pagers and there group settings ordered with thesystem.To change the access level, press the ✔ button and enter a numeric value, the designated Pager Group.The default setting is 1. See section 4.2.10 for more information on the use of Pager Groups.Note: This parameter is only relevant when either of the ‘Transmit’ actions are configured.4.2.3.6 Trigger SleepComThe “Trig’ SleepCom” option is used to denote whether this input will be used to trigger a SleepCom unitassociated with the system.To change the monitored parameter, press the ✔ button to toggle between YES and NO.The default setting is YES.Note: This parameter is only relevant when either of the ‘Transmit’ actions are configured.