V1.00, August 30, 2004135. Close the elbow, forming a 90 degree right angle. Tighten the domedstrain relief until the insert is tight against the probe cable.3.3.2 TTC-PROBE-11 InstallationProbe type TTC-PROBE-11 allows coupling of flexible conduit directly to thethermometer well adapter fittings provided. Its unique design allows the probe tobe held in the well. Figure 3.6 illustrates this assembly.Figure 3.6: PROBE-11 InstallationTo install the probe into the thermo well:1. Select the appropriate thermo well adapter fitting and either wrap the malethreads with Teflon tape or coat with suitable pipe dope compound. Oncethe male threads are prepared, thread the adapter fittings into the thermowell.2. If the probe well’s ID is greater than 0.390 select the appropriate probesleeve and slide over the probe. Tighten the set screw with theaccompanying Allen Key.3. Slide the probe into the thermo well.4. Thread the appropriate brass fitting into the thermometer well. Thiscompresses the spring and holds the probe at the end of the well.5. Thread the appropriate conduit fitting into the ½-NPT female threads.3.3.3 Magnetic Mount Probe (TTC-PROBE-02) InstallationA magnetic mount probe (P/N: TTC-PROBE-02-xxx) is available for surfacemounting to the LTC or transformer tank when a thermo well is unavailable.To mount the probe you will need:1 / 2 N P TLiquid TightFittingNot IncludedFlexible ConduitNot IncludedBrass Fittings(Included)W a s h e r(Included) Spring(Included) W a s h e r(Included)P r o b eT h e r m o m e t e r W e l lP r o b eS l e e v e(Included)