V1.00, August 30, 200469Press YES when you have made the correct selection. Selecting DSABL willblock the device alarm relay and the front panel alarm LED from illuminating.However, the front panel will display the alarm if present.For programming from a PC just type the setting for temperature probe alarmenable on the “Enter:” line as follows:Enter:117/1)This will disable the temperature probe alarm. Type 0 to enable the alarm.4.13.3 Manual Mode Alarm SettingThe MANUAL alarm occurs anytime any of the four outputs is programmed fromAuto Mode to Manual Mode, independent of whether the output is picked up ordropped out. The Manual Mode alarm is for reporting only and does notsupervise any of the control functions.Setting from the front panel, press the %%%%or &&&&arrow button until the setting 111 isdisplayed:Press the YES button. The first character will flash. Use the %%%% or &&&&arrow buttonsto scroll between ENABL (enable) and DSABL (disable).Press YES when you have made the correct selection. Selecting DSABL willblock the device alarm relay and the front panel alarm LED from illuminating.However, the front panel will display the alarm if present.For programming from a PC just type the setting for manual mode alarm enableon the “Enter:” line as follows:Enter:118/1)This will disable the manual mode alarm. Type 0 to enable the alarm.4.13.4 Winding Circuit Alarm SettingThe WNDCKT alarm occurs anytime the TOP OIL temperature exceeds 54°C inunits that are equipped to measure load current. These are models –XX3X orPRGM SETTING 111MANALRM=ENABLPRGM SETTING 110TPROBEALRM=DSABL