SpecificationsRadio Range1900 MHz, 150 mW: Up to 4.8 km (3 miles)2.4 GHz, 65 mW: Up to 3.2 km (2 miles)Minimum Separation Distance900 MHz (150 mW): 2 m (6 ft)2.4 GHz (65 mW): 0.3 m (1 ft)Transmit Power900 MHz, 150 mW: 21 dBm (150 mW) conducted2.4 GHz, 65 mW: 18 dBm (65 mW) conducted, less than or equal to 20dBm (100 mW) EIRP900 MHz Compliance (150 mW)FCC ID TGUDX80 - This device complies with FCC Part 15, Subpart C,15.247IC: 7044A-DX80092.4 GHz ComplianceFCC ID UE300DX80-2400 - This device complies with FCC Part 15,Subpart C, 15.247ETSI/EN: In accordance with EN 300 328: V1.7.1 (2006-05)IC: 7044A-DX8024Spread Spectrum TechnologyFHSS (Frequency Hopping Spread Spectrum)Link TimeoutGateway: Configurable via User Configuration Tool (UCT) softwareNode: Defined by GatewayDiscrete InputsRating: See control drawingSample/Report Rates: DIP switch configurableDiscrete Input ON ConditionPNP: Greater than 8 VNPN: Less than 0.7 VDiscrete Input OFF Condition (DX99 Models)PNP: Less than 4.5 VNPN: Greater than 2.2 V or openAnalog Input Rating (mA Models)Rating for 4 to 20 mA models: 24 mAImpedance: Approx. 20 OhmsAnalog Input 1 Sample/Report Rates: DIP switch configurableAnalog Input 2 Sample/Report Rates: 1 second / 16 secondsAccuracy: 0.1% of full scale +0.01% per °CResolution: 12-bitAnalog Input Rating (V Models)Rating for 0 to 10V models: 10 VImpedance: Approx. 20 OhmsAnalog Input 1 Sample/Report Rates: DIP switch configurableAnalog Input 2 Sample/Report Rates: 1 second / 16 secondsAccuracy: 0.25% of full scale +0.01% per °CResolution: 12-bitTo verify the analog input's impedance, use an Ohm meterto measure the resistance between the analog inputterminal (AIx) and the ground (GND) terminal.Supply Voltage3.6 V dc low power option from an internal batteryPower ConsumptionConsumption: Application dependantHousingGlass and cast aluminium w/ chromating and chemically resistant paint(outside only)Antenna ConnectionExt. Reverse Polarity SMA, 50 OhmsMax Tightening Torque: 0.45 N·m (4 lbf·in)InterfaceIndicators: Two bi-color LEDsButtons: TwoDisplay: Six character LCDWiring AccessTwo 1/2-inch NPT ports, one 3/4-inch NPT port (internal threads)Environmental RatingIEC IP68 2Operating Conditions3−40 °C to +65 °C (−40 °F to +149 °F) (Electronics); −20 °C to +80°C (−4 °F to +176 °F) (LCD)95% maximum relative humidity (non-condensing)Radiated Immunity: 10 V/m, 80-2700 MHz (EN61000-6-2)Shock and VibrationIEC 68-2-6 and IEC 68-2-27Shock: 30g, 11 millisecond half sine wave, 18 shocksVibration: 0.5 mm p-p, 10 to 60 HzCertificationsCSA: Class I, Division 1, Groups A, B, C, D; Class II, Division 1,Groups E, F, G; Class III, Division 1 (Ex ia IIC T4 / AEx ia IIC T4)Certificate: 2008243LCIE/ATEX: Zone 0 (Category 1G) and 20 (Category 1D),Temperature Class T4 (II 1 GD / Ex ia IIC T4 / Ex iaD 20 IP68 T82°C)Certificate: LCIE 08 ATEX 6098 XSpecial Conditions for Safe Use imposed by Intrinsic Safety CertificateLCIE 08 ATEX 6098 X: Ambient temperature range is –40 to 70 °C.SureCross® DX99 FlexPower devices can only be connected toIntrinsically Safe certified equipment or simple apparatus as defined byEN 60079-11. All connected equipment must comply with the EntityParameters (Safety Parameters) listed in the Control Drawings (p/n141513). The device must only use a lithium battery manufactured byXENO, type XL-205F.Metal Housing DimensionsThe metal housing is used for the DX99...D models.1 Radio range is with the 2 dB antenna that ships with the product. High-gain antennas are available, but the range depends on the environment and line ofsight. To determine the range of your wireless network, perform a Site Survey.2 Refer to the SureCross Wireless I/O Networks Instruction Manual (p/n 132607) for installation and waterproofing instructions.3 Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.SureCross DX99 FlexPower Node (Metal Housing)P/N 142497 Rev. L www.bannerengineering.com - Tel: +1-763-544-3164 11